分类:01_火灾事故报告 / 2018 年份:2018 大小:26.2 KB 知识库创建:2026-08-05 08:20:25 抓取时间:2026-10-22 08:50:22

8 CSIRO

Smoke Sensitivity Testing of Residential Smoke Alarms

Commercial-in-Confidence

Prepared for:

Fire and Rescue NSW - Fire Investigation and Research Unit

Amarina Avenue

Greenacre, NSW, 2190

AUSTRALIA

Agreement: 2016030735

Report: XF3033/R3

Issue date: 17 May 2016

Report XF3033/R3 Smoke Sensitivity Testing of Residential Smoke Alarms

Prepared on behalf of CSIRO by

NameAlex Tang
PositionResearch Projects Officer, Fire Systems
Date17 May 2016

Reviewed by

NameDr Christopher Preston
PositionTeam Leader- Fire Systems
Date17 May 2016
Signature![](359,775,619,861)

Commonwealth Scientific and Industrial Research Organisation Infrastructure TechnologiesFire Systems and Acoustics

Gate 5, 2 Normanby Road(East Reception, Rivett Building 001)CLAYTON, VICAUSTRALIA, 3168

Ph.: +61 (0)3 9545 2777

Fax: +61 (0)3 9544 1128

Web: http://www.csiro.au

Copyright and Disclaimer

To the extent permitted by law, all rights are reserved and no part of this publication covered by copyright may be reproduced or copied in any form or by any means except with the written permission of CSIRO.

CSIRO reports apply only to the specific samples investigated under the stated criteria and conditions. It is the client's responsibility to assure that production units of the products are of identical manufacture. CSIRO shall have no liability for deductions, inferences or generalisations drawn by the client or others from reports issued by CSIRO. This report shall not be used to claim, constitute or imply product endorsement by CSIRO

Report XF3033/R3 Smoke Sensitivity Testing of Residential Smoke Alarms

Table of contents

1 INTRODUCTION $\ldots$ 4

2 TEST PROGRAM $\ldots$ 4

  1. 1 Test Samples $\ldots$ 4

3 TEST RESULTS $\ldots$ 5

  1. 1 Directional Dependence Test Results $\ldots$ 5
  1. 2 Initial Sensitivity Test Results $\ldots$ 7

4 REFERENCE INFORMATION $\ldots$ 19

  1. 1 Obscuration vs. Ionisation data $\ldots$ 19
  1. 2 Obscuration units $\ldots$ 19

List of tables

Table 1 Summary of the submitted samples of each of four models of residential smoke alarm. 4

List of figures

Figure 1. Polar chart of directional dependence test results of XF3033/333 (P107). 5

Figure 2. Polar chart of directional dependence test results of XF3033/357 (M107)....................6

Figure 3. Typical response values of the reference obscurometer and MIC, as fitted to the CSIRO AS 3786 / AS 7240.7 test tunnel, to aspirated paraffin during tunnel sensitivity tests of smoke alarms and detectors. 19

Figure 4. Relationship between smoke density as measured in dB/m and %obs/m to 10 %obs/m.

Figure 5. Relationship between smoke density as measured in dB/m and %obs/m to 50 %obs/m.

Report XF3033/R3 Smoke Sensitivity Testing of Residential Smoke Alarms

1 INTRODUCTION

Fire and Rescue NSW submitted samples of four different models of residential smoke alarm for Directional Dependence and Initial Sensitivity testing in accordance with AS 3786-2014.

This report replaced CSRO report XF3033/R2 dated 13 May 2016.

2 TEST PROGRAM

The following activities were performed to evaluate the sensitivity of each model of residential smoke alarm:

● Directional Dependence (Clause 5.2) test (one test on one sample of each of the four models); and

● Initial sensitivity (alarm response threshold) test (Clause 5.3) on all samples of each model.

The results of these tests are detailed in Section 3 of this report.

2.1 Test Samples

A summary of the submitted samples are detailed in Table 1 of this report.

Table 1 Summary of the submitted samples of each of four models of residential smoke alarm.

CSIRO sample identificationClient identificationSmoke Alarm Type
XF3033/241 - XF3033/286P061 - P0106Photoelectric
XF3033/287 - XF3033/332M061 - M106Photoelectric
XF3033/333 - XF3033/356P107 - P130Photoelectric
XF3033/357 - XF3033/380M107 - M130Photoelectric
XF3033/381 - XF3033/452D061 - $D132^{1}$Photoelectric & Ionisation
XF3033/453 - XF3033/524I061 - I132Ionisation

Report XF3033/R3 Smoke Sensitivity Testing of Residential Smoke Alarms

3 TEST RESULTS

3.1 Directional Dependence Test Results

XF3033/333 (P107)

SampleOrientation (°)Response Threshold Value, m (dB/m)Ambient Air Temp (°C) & Relative Humidity (%RH)Maximum / Minimum Sensitivity orientation
XF3033/01 (P001)00.09320/51-
XF3033/01 (P001)450.09120/51-
XF3033/01 (P001)900.09420/51-
XF3033/01 (P001)1350.09620/51Min
XF3033/01 (P001)1800.09220/51-
XF3033/01 (P001)2250.08420/51Max
XF3033/01 (P001)2700.08420/51-
XF3033/01 (P001)3150.09220/51-

〔图〕插图

Figure 1. Polar chart of directional dependence test results of XF3033/333 (P107).

Report XF3033/R3 Smoke Sensitivity Testing of Residential Smoke Alarms

XF3033/357 (M107)

SampleOrientation (°)Response Threshold Value, m (dB/m)Ambient Air Temp (°C) & Relative Humidity (%RH)Maximum / Minimum Sensitivity orientation
XF3033/61 (M107)00.09024/64-
XF3033/61 (M107)450.08324/63-
XF3033/61 (M107)900.09024/63-
XF3033/61 (M107)1350.09224/62-
XF3033/61 (M107)1800.09924/62Max
XF3033/61 (M107)2250.08924/63-
XF3033/61 (M107)2700.08724/63-
XF3033/61 (M107)3150.08224/62Min

〔图〕插图

Figure 2. Polar chart of directional dependence test results of XF3033/357 (M107).

Report XF3033/R3 Smoke Sensitivity Testing of Residential Smoke Alarms

3.2 Initial Sensitivity Test Results

XF3033/241 (P061) through XF3033/286 (P106)

SampleOrientationResponse Threshold Value (dB/m)Ambient Air Temperature (°C) & Relative Humidity (%RH)Requirement
XF3033/241 (P061)0°0.16120/38m ≥ 0.05 dB/m
XF3033/242 (P062)0°0.13920/38m ≥ 0.05 dB/m
XF3033/243 (P063)0°0.15220/38m ≥ 0.05 dB/m
XF3033/244 (P064)0°0.16720/38m ≥ 0.05 dB/m
XF3033/245 (P065)0°0.17820/37m ≥ 0.05 dB/m
XF3033/246 (P066)0°0.15420/37m ≥ 0.05 dB/m
XF3033/247 (P067)0°0.13220/37m ≥ 0.05 dB/m
XF3033/248 (P068)0°0.12520/37m ≥ 0.05 dB/m
XF3033/249 (P069)0°0.17322/36m ≥ 0.05 dB/m
XF3033/250 (P070)0°0.15220/38m ≥ 0.05 dB/m
XF3033/251 (P071)0°0.17220/38m ≥ 0.05 dB/m
XF3033/252 (P072)0°0.13120/38m ≥ 0.05 dB/m
XF3033/253 (P073)0°0.14022/36m ≥ 0.05 dB/m
XF3033/254 (P074)0°0.15520/38m ≥ 0.05 dB/m
XF3033/255 (P075)0°0.15820/38m ≥ 0.05 dB/m
XF3033/256 (P076)0°0.15420/38m ≥ 0.05 dB/m
XF3033/257 (P077)0°0.14019/38m ≥ 0.05 dB/m
XF3033/258 (P078)0°0.16019/38m ≥ 0.05 dB/m
XF3033/259 (P079)0°0.16219/38m ≥ 0.05 dB/m
XF3033/260 (P080)0°0.15619/38m ≥ 0.05 dB/m
XF3033/261 (P081)0°0.15919/39m ≥ 0.05 dB/m
XF3033/262 (P082)0°0.15519/39m ≥ 0.05 dB/m
XF3033/263 (P083)0°0.15119/39m ≥ 0.05 dB/m
XF3033/264 (P084)0°0.16019/39m ≥ 0.05 dB/m
XF3033/265 (P085)0°0.16019/40m ≥ 0.05 dB/m
XF3033/266 (P086)0°0.15119/40m ≥ 0.05 dB/m

Report XF3033/R3 Smoke Sensitivity Testing of Residential Smoke Alarms

SampleOrientationResponse Threshold Value (dB/m)Ambient Air Temperature (°C) & Relative Humidity (%RH)Requirement
XF3033/267 (P087)0°0.15619/40m ≥ 0.05 dB/m
XF3033/268 (P088)0°0.14619/40m ≥ 0.05 dB/m
XF3033/269 (P089)0°0.17419/39m ≥ 0.05 dB/m
XF3033/270 (P090)0°0.16819/39m ≥ 0.05 dB/m
XF3033/271 (P091)0°0.15619/39m ≥ 0.05 dB/m
XF3033/272 (P092)0°0.15622/36m ≥ 0.05 dB/m
XF3033/273 (P093)0°0.18322/40m ≥ 0.05 dB/m
XF3033/274 (P094)0°0.16922/36m ≥ 0.05 dB/m
XF3033/275 (P095)0°0.16221/38m ≥ 0.05 dB/m
XF3033/276 (P096)0°0.14021/38m ≥ 0.05 dB/m
XF3033/277 (P097)0°0.17221/37m ≥ 0.05 dB/m
XF3033/278 (P098)0°0.14721/37m ≥ 0.05 dB/m
XF3033/279 (P099)0°0.17021/37m ≥ 0.05 dB/m
XF3033/280 (P100)0°0.16521/37m ≥ 0.05 dB/m
XF3033/281 (P101)0°0.14221/36m ≥ 0.05 dB/m
XF3033/282 (P102)0°0.16021/36m ≥ 0.05 dB/m
XF3033/283 (P103)0°0.17022/36m ≥ 0.05 dB/m
XF3033/284 (P104)0°0.15321/36m ≥ 0.05 dB/m
XF3033/285 (P105)0°0.17222/35m ≥ 0.05 dB/m
XF3033/286 (P106)0°0.16522/35m ≥ 0.05 dB/m

Report XF3033/R3 Smoke Sensitivity Testing of Residential Smoke Alarms

XF3033/287 (M061) through XF3033/332 (M106)

SampleOrientationResponse Threshold Value (dB/m)Ambient Air Temperature (°C) & Relative Humidity (%RH)Requirement
XF3033/287 (M061)315°0.16723/39m ≥ 0.05 dB/m
XF3033/288 (M062)315°0.16123/39m ≥ 0.05 dB/m
XF3033/289 (M063)315°0.16723/39m ≥ 0.05 dB/m
XF3033/290 (M064)315°0.17523/39m ≥ 0.05 dB/m
XF3033/291 (M065)315°0.15823/39m ≥ 0.05 dB/m
XF3033/292 (M066)315°0.16823/39m ≥ 0.05 dB/m
XF3033/293 (M067)315°0.17123/39m ≥ 0.05 dB/m
XF3033/294 (M068)315°0.17823/39m ≥ 0.05 dB/m
XF3033/295 (M069)315°0.15824/38m ≥ 0.05 dB/m
XF3033/296 (M070)315°0.17824/38m ≥ 0.05 dB/m
XF3033/297 (M071)315°0.17224/38m ≥ 0.05 dB/m
XF3033/298 (M072)315°0.17024/38m ≥ 0.05 dB/m
XF3033/299 (M073)315°0.17023/38m ≥ 0.05 dB/m
XF3033/300 (M074)315°0.16223/38m ≥ 0.05 dB/m
XF3033/301 (M075)315°0.17723/38m ≥ 0.05 dB/m
XF3033/302 (M076)315°0.16223/38m ≥ 0.05 dB/m
XF3033/303 (M077)315°0.16423/38m ≥ 0.05 dB/m
XF3033/304 (M078)315°0.15623/38m ≥ 0.05 dB/m
XF3033/305 (M079)315°0.16623/38m ≥ 0.05 dB/m
XF3033/306 (M080)315°0.16923/38m ≥ 0.05 dB/m
XF3033/307 (M081)315°0.18023/38m ≥ 0.05 dB/m
XF3033/308 (M082)315°0.16323/38m ≥ 0.05 dB/m
XF3033/309 (M083)315°0.19123/38m ≥ 0.05 dB/m
XF3033/310 (M084)315°0.17223/38m ≥ 0.05 dB/m
XF3033/311 (M085)315°0.17024/38m ≥ 0.05 dB/m
XF3033/312 (M086)315°0.15824/38m ≥ 0.05 dB/m

Report XF3033/R3 Smoke Sensitivity Testing of Residential Smoke Alarms

SampleOrientationResponse Threshold Value (dB/m)Ambient Air Temperature (°C) & Relative Humidity (%RH)Requirement
XF3033/313 (M087)315°0.18224/38m ≥ 0.05 dB/m
XF3033/314 (M088)315°0.18724/38m ≥ 0.05 dB/m
XF3033/315 (M089)315°0.18922/40m ≥ 0.05 dB/m
XF3033/316 (M090)315°0.18024/38m ≥ 0.05 dB/m
XF3033/317 (M091)315°0.19624/38m ≥ 0.05 dB/m
XF3033/318 (M092)315°0.16622/40m ≥ 0.05 dB/m
XF3033/319 (M093)315°0.17923/38m ≥ 0.05 dB/m
XF3033/320 (M094)315°0.17523/38m ≥ 0.05 dB/m
XF3033/321 (M095)315°0.18223/38m ≥ 0.05 dB/m
XF3033/322 (M096)315°0.17323/38m ≥ 0.05 dB/m
XF3033/323 (M097)315°0.16423/39m ≥ 0.05 dB/m
XF3033/324 (M098)315°0.16723/39m ≥ 0.05 dB/m
XF3033/325 (M099)315°0.16223/39m ≥ 0.05 dB/m
XF3033/326 (M100)315°0.18623/39m ≥ 0.05 dB/m
XF3033/327 (M101)315°0.16622/39m ≥ 0.05 dB/m
XF3033/328 (M102)315°0.15522/39m ≥ 0.05 dB/m
XF3033/329 (M103)315°0.17122/39m ≥ 0.05 dB/m
XF3033/330 (M104)315°0.17122/39m ≥ 0.05 dB/m
XF3033/331 (M105)315°0.17822/40m ≥ 0.05 dB/m
XF3033/332 (M106)315°0.17322/40m ≥ 0.05 dB/m

Report XF3033/R3 Smoke Sensitivity Testing of Residential Smoke Alarms

XF3033/333 (P107) through XF3033/356 (P130)

SampleOrientationResponse Threshold Value (dB/m)Ambient Air Temperature (°C) & Relative Humidity (%RH)Requirement
XF3033/333 (P107)135°0.09219/50m ≥ 0.05 dB/m
XF3033/334 (P108)135°0.08319/50m ≥ 0.05 dB/m
XF3033/335 (P109)135°0.09118/49m ≥ 0.05 dB/m
XF3033/336 (P110)135°0.07118/49m ≥ 0.05 dB/m
XF3033/337 (P111)135°Permanent Alarm StateNot testedm ≥ 0.05 dB/m
XF3033/338 (P112)135°0.06819/51m ≥ 0.05 dB/m
XF3033/339 (P113)135°0.08919/51m ≥ 0.05 dB/m
XF3033/340 (P114)135°0.08818/51m ≥ 0.05 dB/m
XF3033/341 (P115)135°0.08418/51m ≥ 0.05 dB/m
XF3033/342 (P116)135°0.09019/52m ≥ 0.05 dB/m
XF3033/343 (P117)135°0.08519/52m ≥ 0.05 dB/m
XF3033/344 (P118)135°0.08619/52m ≥ 0.05 dB/m
XF3033/345 (P119)135°0.07819/52m ≥ 0.05 dB/m
XF3033/346 (P120)135°0.07719/52m ≥ 0.05 dB/m
XF3033/347 (P121)135°0.08419/52m ≥ 0.05 dB/m
XF3033/348 (P122)135°0.08619/52m ≥ 0.05 dB/m
XF3033/349 (P123)135°0.08619/52m ≥ 0.05 dB/m
XF3033/350 (P124)135°0.06819/52m ≥ 0.05 dB/m
XF3033/351 (P125)135°0.08619/52m ≥ 0.05 dB/m
XF3033/352 (P126)135°0.09019/52m ≥ 0.05 dB/m
XF3033/353 (P127)135°0.08819/52m ≥ 0.05 dB/m
XF3033/354 (P128)135°0.08119/53m ≥ 0.05 dB/m
XF3033/355 (P129)135°0.08519/53m ≥ 0.05 dB/m
XF3033/356 (P130)135°0.08619/53m ≥ 0.05 dB/m

Report XF3033/R3 Smoke Sensitivity Testing of Residential Smoke Alarms

XF3033/357 (M107) through XF3033/380 (M130)

SampleOrientationResponse Threshold Value (dB/m)Ambient Air Temperature (°C) & Relative Humidity (%RH)Requirement
XF3033/357 (M107)180°0.08024/54m ≥ 0.05 dB/m
XF3033/358 (M108)180°0.10324/54m ≥ 0.05 dB/m
XF3033/359 (M109)180°0.11324/54m ≥ 0.05 dB/m
XF3033/360 (M110)180°0.10724/54m ≥ 0.05 dB/m
XF3033/361 (M111)180°0.09024/53m ≥ 0.05 dB/m
XF3033/362 (M112)180°0.07424/53m ≥ 0.05 dB/m
XF3033/363 (M113)180°0.10024/53m ≥ 0.05 dB/m
XF3033/364 (M114)180°0.08824/53m ≥ 0.05 dB/m
XF3033/365 (M115)180°0.09124/51m ≥ 0.05 dB/m
XF3033/366 (M116)180°0.09224/51m ≥ 0.05 dB/m
XF3033/367 (M117)180°0.09324/51m ≥ 0.05 dB/m
XF3033/368 (M118)180°0.09624/51m ≥ 0.05 dB/m
XF3033/369 (M119)180°0.09624/51m ≥ 0.05 dB/m
XF3033/370 (M120)180°0.07824/51m ≥ 0.05 dB/m
XF3033/371 (M121)180°0.08924/51m ≥ 0.05 dB/m
XF3033/372 (M122)180°0.09924/51m ≥ 0.05 dB/m
XF3033/373 (M123)180°0.13024/50m ≥ 0.05 dB/m
XF3033/374 (M124)180°0.08324/50m ≥ 0.05 dB/m
XF3033/375 (M125)180°0.13124/50m ≥ 0.05 dB/m
XF3033/376 (M126)180°0.09224/50m ≥ 0.05 dB/m
XF3033/377 (M127)180°0.08424/49m ≥ 0.05 dB/m
XF3033/378 (M128)180°0.07424/49m ≥ 0.05 dB/m
XF3033/379 (M129)180°0.09224/49m ≥ 0.05 dB/m
XF3033/380 (M130)180°0.08824/49m ≥ 0.05 dB/m

Report XF3033/R3 Smoke Sensitivity Testing of Residential Smoke Alarms

XF3033/381 (D061) through XF3033/452 (D132)

SampleOrientationResponse Threshold Value (dB/m)Ambient Air Temperature (°C) & Relative Humidity (%RH)Requirement
XF3033/381 (D061)0°0.08022/52m ≥ 0.05 dB/m
XF3033/382 (D062)0°0.07222/52m ≥ 0.05 dB/m
XF3033/383 (D063)0°0.07122/52m ≥ 0.05 dB/m
XF3033/384 (D064)0°0.06422/52m ≥ 0.05 dB/m
XF3033/385 (D065)0°0.08322/53m ≥ 0.05 dB/m
XF3033/386 (D066)0°0.06922/53m ≥ 0.05 dB/m
XF3033/387 (D067)0°0.05822/53m ≥ 0.05 dB/m
XF3033/388 (D068)0°0.05922/53m ≥ 0.05 dB/m
XF3033/389 (D069)0°0.09622/53m ≥ 0.05 dB/m
XF3033/390 (D070)0°0.07322/53m ≥ 0.05 dB/m
XF3033/391 (D071)0°0.07122/53m ≥ 0.05 dB/m
XF3033/392 (D072)0°0.06922/53m ≥ 0.05 dB/m
XF3033/393 (D073)0°0.07822/53m ≥ 0.05 dB/m
XF3033/394 (D074)0°0.07422/53m ≥ 0.05 dB/m
XF3033/395 (D075)0°0.07422/53m ≥ 0.05 dB/m
XF3033/396 (D076)0°0.08822/53m ≥ 0.05 dB/m
XF3033/397 (D077)0°0.09622/53m ≥ 0.05 dB/m
XF3033/398 (D078)0°0.05722/53m ≥ 0.05 dB/m
XF3033/399 (D079)0°0.06822/53m ≥ 0.05 dB/m
XF3033/400 (D080)0°0.07022/53m ≥ 0.05 dB/m
XF3033/401 (D081)0°0.12823/52m ≥ 0.05 dB/m
XF3033/402 (D082)0°0.07623/52m ≥ 0.05 dB/m
XF3033/403 (D083)0°0.08923/52m ≥ 0.05 dB/m
XF3033/404 (D084)0°0.09823/52m ≥ 0.05 dB/m
XF3033/405 (D085)0°0.07023/50m ≥ 0.05 dB/m
XF3033/406 (D086)0°0.05923/50m ≥ 0.05 dB/m
XF3033/407 (D087)0°0.07923/50m ≥ 0.05 dB/m

Report XF3033/R3 Smoke Sensitivity Testing of Residential Smoke Alarms

SampleOrientationResponse Threshold Value (dB/m)Ambient Air Temperature (°C) & Relative Humidity (%RH)Requirement
XF3033/408 (D088)0°0.09623/50m ≥ 0.05 dB/m
XF3033/409 (D089)0°0.07123/49m ≥ 0.05 dB/m
XF3033/410 (D090)0°0.07823/49m ≥ 0.05 dB/m
XF3033/411 (D091)0°0.09523/49m ≥ 0.05 dB/m
XF3033/412 (D092)0°0.07023/49m ≥ 0.05 dB/m
XF3033/413 (D093)0°0.08923/49m ≥ 0.05 dB/m
XF3033/414 (D094)0°0.06823/49m ≥ 0.05 dB/m
XF3033/415 (D095)0°0.07223/49m ≥ 0.05 dB/m
XF3033/416 (D096)0°0.08923/49m ≥ 0.05 dB/m
XF3033/417 (D097)0°0.08423/48m ≥ 0.05 dB/m
XF3033/418 (D098)0°0.06623/48m ≥ 0.05 dB/m
XF3033/419 (D099)0°0.06123/48m ≥ 0.05 dB/m
XF3033/420 (D100)0°0.07823/48m ≥ 0.05 dB/m
XF3033/421 (D101)0°0.08423/44m ≥ 0.05 dB/m
XF3033/422 (D102)0°0.08023/44m ≥ 0.05 dB/m
XF3033/423 (D103)0°0.07523/44m ≥ 0.05 dB/m
XF3033/424 (D104)0°0.07823/44m ≥ 0.05 dB/m
XF3033/425 (D105)0°0.08822/45m ≥ 0.05 dB/m
XF3033/426 (D106)0°0.06122/45m ≥ 0.05 dB/m
XF3033/427 (D107)0°0.09622/45m ≥ 0.05 dB/m
XF3033/428 (D108)0°0.09222/45m ≥ 0.05 dB/m
XF3033/429 (D109)0°0.08122/44m ≥ 0.05 dB/m
XF3033/430 (D110)0°0.06922/44m ≥ 0.05 dB/m
XF3033/431 (D111)0°0.06222/44m ≥ 0.05 dB/m
XF3033/432 (D112)0°0.06422/44m ≥ 0.05 dB/m
XF3033/433 (D113)0°0.05822/45m ≥ 0.05 dB/m
XF3033/434 (D114)0°0.06422/45m ≥ 0.05 dB/m
XF3033/435 (D115)0°0.07122/45m ≥ 0.05 dB/m

Report XF3033/R3 Smoke Sensitivity Testing of Residential Smoke Alarms

SampleOrientationResponse Threshold Value (dB/m)Ambient Air Temperature (°C) & Relative Humidity (%RH)Requirement
XF3033/436 (D116)0°0.07322/45m ≥ 0.05 dB/m
XF3033/437 (D117)0°0.06622/44m ≥ 0.05 dB/m
XF3033/438 (D118)0°0.09622/44m ≥ 0.05 dB/m
XF3033/439 (D119)0°0.07622/44m ≥ 0.05 dB/m
XF3033/440 (D120)0°0.05722/44m ≥ 0.05 dB/m
XF3033/441 (D121)0°0.10222/44m ≥ 0.05 dB/m
XF3033/442 (D122)0°0.07422/44m ≥ 0.05 dB/m
XF3033/443 (D123)0°0.08022/44m ≥ 0.05 dB/m
XF3033/444 (D124)0°0.08722/44m ≥ 0.05 dB/m
XF3033/445 (D125)0°0.07122/43m ≥ 0.05 dB/m
XF3033/446 (D126)0°0.06222/43m ≥ 0.05 dB/m
XF3033/447 (D127)0°0.07422/43m ≥ 0.05 dB/m
XF3033/448 (D128)0°0.07322/43m ≥ 0.05 dB/m
XF3033/449 (D129)0°0.07022/42m ≥ 0.05 dB/m
XF3033/450 (D130)0°0.06822/42m ≥ 0.05 dB/m
XF3033/451 (D131)0°0.08622/42m ≥ 0.05 dB/m
XF3033/452 (D132)0°0.08322/42m ≥ 0.05 dB/m

Report XF3033/R3 Smoke Sensitivity Testing of Residential Smoke Alarms

XF3033/453 (I061) through XF3033/524 (I132)

SampleOrientationResponse Threshold Value (MIC y)Ambient Air Temperature (°C) & Relative Humidity (%RH)Requirement
XF3033/453 (I061)0°0.8522/400.05 ≤ Δy/Δt ≤ 0.3
XF3033/454 (I062)0°0.7022/400.05 ≤ Δy/Δt ≤ 0.3
XF3033/455 (I063)0°0.7922/400.05 ≤ Δy/Δt ≤ 0.3
XF3033/456 (I064)0°0.7422/400.05 ≤ Δy/Δt ≤ 0.3
XF3033/457 (I065)0°0.8021/400.05 ≤ Δy/Δt ≤ 0.3
XF3033/458 (I066)0°0.7121/400.05 ≤ Δy/Δt ≤ 0.3
XF3033/459 (I067)0°0.8521/400.05 ≤ Δy/Δt ≤ 0.3
XF3033/460 (I068)0°0.7121/400.05 ≤ Δy/Δt ≤ 0.3
XF3033/461 (I069)0°0.8421/400.05 ≤ Δy/Δt ≤ 0.3
XF3033/462 (I070)0°0.7021/400.05 ≤ Δy/Δt ≤ 0.3
XF3033/463 (I071)0°0.7821/400.05 ≤ Δy/Δt ≤ 0.3
XF3033/464 (I072)0°0.8221/400.05 ≤ Δy/Δt ≤ 0.3
XF3033/465 (I073)0°0.7621/390.05 ≤ Δy/Δt ≤ 0.3
XF3033/466 (I074)0°0.7821/390.05 ≤ Δy/Δt ≤ 0.3
XF3033/467 (I075)0°0.9021/390.05 ≤ Δy/Δt ≤ 0.3
XF3033/468 (I076)0°0.7521/390.05 ≤ Δy/Δt ≤ 0.3
XF3033/469 (I077)0°0.8623/400.05 ≤ Δy/Δt ≤ 0.3
XF3033/470 (I078)0°0.6823/400.05 ≤ Δy/Δt ≤ 0.3
XF3033/471 (I079)0°0.7223/400.05 ≤ Δy/Δt ≤ 0.3
XF3033/472 (I080)0°0.7823/400.05 ≤ Δy/Δt ≤ 0.3
XF3033/473 (I081)0°0.7223/400.05 ≤ Δy/Δt ≤ 0.3
XF3033/474 (I082)0°0.7223/400.05 ≤ Δy/Δt ≤ 0.3
XF3033/475 (I083)0°0.7323/400.05 ≤ Δy/Δt ≤ 0.3
XF3033/476 (I084)0°0.7523/400.05 ≤ Δy/Δt ≤ 0.3
XF3033/477 (I085)0°0.7423/400.05 ≤ Δy/Δt ≤ 0.3
XF3033/478 (I086)0°0.7423/400.05 ≤ Δy/Δt ≤ 0.3
XF3033/479 (I087)0°0.7123/400.05 ≤ Δy/Δt ≤ 0.3

Report XF3033/R3 Smoke Sensitivity Testing of Residential Smoke Alarms

SampleOrientationResponse Threshold Value (MIC y)Ambient Air Temperature (°C) & Relative Humidity (%RH)Requirement
XF3033/480 (I088)0°0.7423/40$0.05 \le \Delta y/\Delta t \le 0.3$
XF3033/481 (I089)0°0.7523/40$0.05 \le \Delta y/\Delta t \le 0.3$
XF3033/482 (I090)0°0.7823/40$0.05 \le \Delta y/\Delta t \le 0.3$
XF3033/483 (I091)0°0.9523/40$0.05 \le \Delta y/\Delta t \le 0.3$
XF3033/484 (I092)0°0.8323/40$0.05 \le \Delta y/\Delta t \le 0.3$
XF3033/485 (I093)0°0.7523/39$0.05 \le \Delta y/\Delta t \le 0.3$
XF3033/486 (I094)0°0.8023/39$0.05 \le \Delta y/\Delta t \le 0.3$
XF3033/487 (I095)0°0.6923/39$0.05 \le \Delta y/\Delta t \le 0.3$
XF3033/488 (I096)0°0.6823/39$0.05 \le \Delta y/\Delta t \le 0.3$
XF3033/489 (I097)0°0.6922/39$0.05 \le \Delta y/\Delta t \le 0.3$
XF3033/490 (I098)0°0.7122/39$0.05 \le \Delta y/\Delta t \le 0.3$
XF3033/491 (I099)0°0.7822/39$0.05 \le \Delta y/\Delta t \le 0.3$
XF3033/492 (I100)0°0.7222/39$0.05 \le \Delta y/\Delta t \le 0.3$
XF3033/493 (I101)0°0.7222/40$0.05 \le \Delta y/\Delta t \le 0.3$
XF3033/494 (I102)0°0.6822/40$0.05 \le \Delta y/\Delta t \le 0.3$
XF3033/495 (I103)0°0.8522/40$0.05 \le \Delta y/\Delta t \le 0.3$
XF3033/496 (I104)0°0.6522/40$0.05 \le \Delta y/\Delta t \le 0.3$
XF3033/497 (I105)0°0.8522/40$0.05 \le \Delta y/\Delta t \le 0.3$
XF3033/498 (I106)0°0.7222/40$0.05 \le \Delta y/\Delta t \le 0.3$
XF3033/499 (I107)0°0.7122/40$0.05 \le \Delta y/\Delta t \le 0.3$
XF3033/500 (I108)0°0.7922/40$0.05 \le \Delta y/\Delta t \le 0.3$
XF3033/501 (I109)0°0.7122/40$0.05 \le \Delta y/\Delta t \le 0.3$
XF3033/502 (I110)0°0.7122/40$0.05 \le \Delta y/\Delta t \le 0.3$
XF3033/503 (I111)0°0.7822/40$0.05 \le \Delta y/\Delta t \le 0.3$
XF3033/504 (I112)0°0.8722/40$0.05 \le \Delta y/\Delta t \le 0.3$
XF3033/505 (I113)0°0.7522/40$0.05 \le \Delta y/\Delta t \le 0.3$
XF3033/506 (I114)0°0.7822/40$0.05 \le \Delta y/\Delta t \le 0.3$
XF3033/507 (I115)0°0.7422/40$0.05 \le \Delta y/\Delta t \le 0.3$

Report XF3033/R3 Smoke Sensitivity Testing of Residential Smoke Alarms

SampleOrientationResponse Threshold Value (MIC y)Ambient Air Temperature (°C) & Relative Humidity (%RH)Requirement
XF3033/508 (I116)0°0.7422/400.05 ≤ Δy/Δt ≤ 0.3
XF3033/509 (I117)0°0.8522/400.05 ≤ Δy/Δt ≤ 0.3
XF3033/510 (I118)0°0.7722/400.05 ≤ Δy/Δt ≤ 0.3
XF3033/511 (I119)0°0.8522/400.05 ≤ Δy/Δt ≤ 0.3
XF3033/512 (I120)0°0.7722/400.05 ≤ Δy/Δt ≤ 0.3
XF3033/513 (I121)0°0.8421/400.05 ≤ Δy/Δt ≤ 0.3
XF3033/514 (I122)0°0.7521/400.05 ≤ Δy/Δt ≤ 0.3
XF3033/515 (I123)0°0.7121/400.05 ≤ Δy/Δt ≤ 0.3
XF3033/516 (I124)0°0.7121/400.05 ≤ Δy/Δt ≤ 0.3
XF3033/517 (I125)0°0.6821/400.05 ≤ Δy/Δt ≤ 0.3
XF3033/518 (I126)0°0.7821/400.05 ≤ Δy/Δt ≤ 0.3
XF3033/519 (I127)0°0.6921/400.05 ≤ Δy/Δt ≤ 0.3
XF3033/520 (I128)0°0.8121/400.05 ≤ Δy/Δt ≤ 0.3
XF3033/521 (I129)0°0.7621/400.05 ≤ Δy/Δt ≤ 0.3
XF3033/522 (I130)0°0.7621/400.05 ≤ Δy/Δt ≤ 0.3
XF3033/523 (I131)0°0.8721/400.05 ≤ Δy/Δt ≤ 0.3
XF3033/524 (I132)0°0.6721/400.05 ≤ Δy/Δt ≤ 0.3

Report XF3033/R3 Smoke Sensitivity Testing of Residential Smoke Alarms

4 REFERENCE INFORMATION

The following information is provided to assist in the interpreting of the results detailed in this report.

4.1 Obscuration vs. Ionisation data

The data shown in Figure 3 demonstrates the relationship between smoke density measured by the reference IR obscurometer (measured in dB/m) and by the reference measuring ionisation chamber (MIC, measured in terms of “MIC y”). Refer to Section C2 of AS 3786:2014 for details of the MIC and its response values.

〔图〕插图

Figure 3. Typical response values of the reference obscuometer and MIC, as fitted to the CSIRO AS 3786 / AS 7240.7 test tunnel, to aspirated paraffin during tunnel sensitivity tests of smoke alarms and detectors.

4.2 Obscuration units

The data shown in Figure 4 and Figure 5 demonstrates the relationship between smoke density calculated in terms of the units of dB/m and %obscuration/m.

Report XF3033/R3 Smoke Sensitivity Testing of Residential Smoke Alarms

〔图〕插图

Figure 4. Relationship between smoke density as measured in dB/m and %obs/m to 10 %obs/m.

〔图〕插图

Figure 5. Relationship between smoke density as measured in dB/m and %obs/m to 50 %obs/m.

源文件:01_火灾事故报告/2018/2018_澳洲_FRNSW_住宅烟雾报警器验证测试CSIRO_R3_火灾技术报告.md
‹ 上一篇:2018_上海市人民政府关于同意上海赛科石油化工有限责任公司
下一篇:2018_黄岛区11·23徐州泰威海洋工程有限公司一般火灾事 ›