2018_澳洲_FRNSW_住宅烟雾报警器验证测试CSIRO_R3_火灾技术报告.pdf
8 CSIRO
Smoke Sensitivity Testing of Residential Smoke Alarms
Commercial-in-Confidence
Prepared for:
Fire and Rescue NSW - Fire Investigation and Research Unit
Amarina Avenue
Greenacre, NSW, 2190
AUSTRALIA
Agreement: 2016030735
Report: XF3033/R3
Issue date: 17 May 2016
Report XF3033/R3 Smoke Sensitivity Testing of Residential Smoke Alarms
Prepared on behalf of CSIRO by
| Name | Alex Tang |
|---|---|
| Position | Research Projects Officer, Fire Systems |
| Date | 17 May 2016 |
Reviewed by
| Name | Dr Christopher Preston |
|---|---|
| Position | Team Leader- Fire Systems |
| Date | 17 May 2016 |
| Signature |  |
Commonwealth Scientific and Industrial Research Organisation Infrastructure TechnologiesFire Systems and Acoustics
Gate 5, 2 Normanby Road(East Reception, Rivett Building 001)CLAYTON, VICAUSTRALIA, 3168
Ph.: +61 (0)3 9545 2777
Fax: +61 (0)3 9544 1128
Web: http://www.csiro.au
Copyright and Disclaimer
To the extent permitted by law, all rights are reserved and no part of this publication covered by copyright may be reproduced or copied in any form or by any means except with the written permission of CSIRO.
CSIRO reports apply only to the specific samples investigated under the stated criteria and conditions. It is the client's responsibility to assure that production units of the products are of identical manufacture. CSIRO shall have no liability for deductions, inferences or generalisations drawn by the client or others from reports issued by CSIRO. This report shall not be used to claim, constitute or imply product endorsement by CSIRO
Report XF3033/R3 Smoke Sensitivity Testing of Residential Smoke Alarms
Table of contents
1 INTRODUCTION $\ldots$ 4
2 TEST PROGRAM $\ldots$ 4
- 1 Test Samples $\ldots$ 4
3 TEST RESULTS $\ldots$ 5
- 1 Directional Dependence Test Results $\ldots$ 5
- 2 Initial Sensitivity Test Results $\ldots$ 7
4 REFERENCE INFORMATION $\ldots$ 19
- 1 Obscuration vs. Ionisation data $\ldots$ 19
- 2 Obscuration units $\ldots$ 19
List of tables
Table 1 Summary of the submitted samples of each of four models of residential smoke alarm. 4
List of figures
Figure 1. Polar chart of directional dependence test results of XF3033/333 (P107). 5
Figure 2. Polar chart of directional dependence test results of XF3033/357 (M107)....................6
Figure 3. Typical response values of the reference obscurometer and MIC, as fitted to the CSIRO AS 3786 / AS 7240.7 test tunnel, to aspirated paraffin during tunnel sensitivity tests of smoke alarms and detectors. 19
Figure 4. Relationship between smoke density as measured in dB/m and %obs/m to 10 %obs/m.
Figure 5. Relationship between smoke density as measured in dB/m and %obs/m to 50 %obs/m.
Report XF3033/R3 Smoke Sensitivity Testing of Residential Smoke Alarms
1 INTRODUCTION
Fire and Rescue NSW submitted samples of four different models of residential smoke alarm for Directional Dependence and Initial Sensitivity testing in accordance with AS 3786-2014.
This report replaced CSRO report XF3033/R2 dated 13 May 2016.
2 TEST PROGRAM
The following activities were performed to evaluate the sensitivity of each model of residential smoke alarm:
● Directional Dependence (Clause 5.2) test (one test on one sample of each of the four models); and
● Initial sensitivity (alarm response threshold) test (Clause 5.3) on all samples of each model.
The results of these tests are detailed in Section 3 of this report.
2.1 Test Samples
A summary of the submitted samples are detailed in Table 1 of this report.
Table 1 Summary of the submitted samples of each of four models of residential smoke alarm.
| CSIRO sample identification | Client identification | Smoke Alarm Type |
|---|---|---|
| XF3033/241 - XF3033/286 | P061 - P0106 | Photoelectric |
| XF3033/287 - XF3033/332 | M061 - M106 | Photoelectric |
| XF3033/333 - XF3033/356 | P107 - P130 | Photoelectric |
| XF3033/357 - XF3033/380 | M107 - M130 | Photoelectric |
| XF3033/381 - XF3033/452 | D061 - $D132^{1}$ | Photoelectric & Ionisation |
| XF3033/453 - XF3033/524 | I061 - I132 | Ionisation |
Report XF3033/R3 Smoke Sensitivity Testing of Residential Smoke Alarms
3 TEST RESULTS
3.1 Directional Dependence Test Results
XF3033/333 (P107)
| Sample | Orientation (°) | Response Threshold Value, m (dB/m) | Ambient Air Temp (°C) & Relative Humidity (%RH) | Maximum / Minimum Sensitivity orientation |
|---|---|---|---|---|
| XF3033/01 (P001) | 0 | 0.093 | 20/51 | - |
| XF3033/01 (P001) | 45 | 0.091 | 20/51 | - |
| XF3033/01 (P001) | 90 | 0.094 | 20/51 | - |
| XF3033/01 (P001) | 135 | 0.096 | 20/51 | Min |
| XF3033/01 (P001) | 180 | 0.092 | 20/51 | - |
| XF3033/01 (P001) | 225 | 0.084 | 20/51 | Max |
| XF3033/01 (P001) | 270 | 0.084 | 20/51 | - |
| XF3033/01 (P001) | 315 | 0.092 | 20/51 | - |
〔图〕插图
Figure 1. Polar chart of directional dependence test results of XF3033/333 (P107).
Report XF3033/R3 Smoke Sensitivity Testing of Residential Smoke Alarms
XF3033/357 (M107)
| Sample | Orientation (°) | Response Threshold Value, m (dB/m) | Ambient Air Temp (°C) & Relative Humidity (%RH) | Maximum / Minimum Sensitivity orientation |
|---|---|---|---|---|
| XF3033/61 (M107) | 0 | 0.090 | 24/64 | - |
| XF3033/61 (M107) | 45 | 0.083 | 24/63 | - |
| XF3033/61 (M107) | 90 | 0.090 | 24/63 | - |
| XF3033/61 (M107) | 135 | 0.092 | 24/62 | - |
| XF3033/61 (M107) | 180 | 0.099 | 24/62 | Max |
| XF3033/61 (M107) | 225 | 0.089 | 24/63 | - |
| XF3033/61 (M107) | 270 | 0.087 | 24/63 | - |
| XF3033/61 (M107) | 315 | 0.082 | 24/62 | Min |
〔图〕插图
Figure 2. Polar chart of directional dependence test results of XF3033/357 (M107).
Report XF3033/R3 Smoke Sensitivity Testing of Residential Smoke Alarms
3.2 Initial Sensitivity Test Results
XF3033/241 (P061) through XF3033/286 (P106)
| Sample | Orientation | Response Threshold Value (dB/m) | Ambient Air Temperature (°C) & Relative Humidity (%RH) | Requirement |
|---|---|---|---|---|
| XF3033/241 (P061) | 0° | 0.161 | 20/38 | m ≥ 0.05 dB/m |
| XF3033/242 (P062) | 0° | 0.139 | 20/38 | m ≥ 0.05 dB/m |
| XF3033/243 (P063) | 0° | 0.152 | 20/38 | m ≥ 0.05 dB/m |
| XF3033/244 (P064) | 0° | 0.167 | 20/38 | m ≥ 0.05 dB/m |
| XF3033/245 (P065) | 0° | 0.178 | 20/37 | m ≥ 0.05 dB/m |
| XF3033/246 (P066) | 0° | 0.154 | 20/37 | m ≥ 0.05 dB/m |
| XF3033/247 (P067) | 0° | 0.132 | 20/37 | m ≥ 0.05 dB/m |
| XF3033/248 (P068) | 0° | 0.125 | 20/37 | m ≥ 0.05 dB/m |
| XF3033/249 (P069) | 0° | 0.173 | 22/36 | m ≥ 0.05 dB/m |
| XF3033/250 (P070) | 0° | 0.152 | 20/38 | m ≥ 0.05 dB/m |
| XF3033/251 (P071) | 0° | 0.172 | 20/38 | m ≥ 0.05 dB/m |
| XF3033/252 (P072) | 0° | 0.131 | 20/38 | m ≥ 0.05 dB/m |
| XF3033/253 (P073) | 0° | 0.140 | 22/36 | m ≥ 0.05 dB/m |
| XF3033/254 (P074) | 0° | 0.155 | 20/38 | m ≥ 0.05 dB/m |
| XF3033/255 (P075) | 0° | 0.158 | 20/38 | m ≥ 0.05 dB/m |
| XF3033/256 (P076) | 0° | 0.154 | 20/38 | m ≥ 0.05 dB/m |
| XF3033/257 (P077) | 0° | 0.140 | 19/38 | m ≥ 0.05 dB/m |
| XF3033/258 (P078) | 0° | 0.160 | 19/38 | m ≥ 0.05 dB/m |
| XF3033/259 (P079) | 0° | 0.162 | 19/38 | m ≥ 0.05 dB/m |
| XF3033/260 (P080) | 0° | 0.156 | 19/38 | m ≥ 0.05 dB/m |
| XF3033/261 (P081) | 0° | 0.159 | 19/39 | m ≥ 0.05 dB/m |
| XF3033/262 (P082) | 0° | 0.155 | 19/39 | m ≥ 0.05 dB/m |
| XF3033/263 (P083) | 0° | 0.151 | 19/39 | m ≥ 0.05 dB/m |
| XF3033/264 (P084) | 0° | 0.160 | 19/39 | m ≥ 0.05 dB/m |
| XF3033/265 (P085) | 0° | 0.160 | 19/40 | m ≥ 0.05 dB/m |
| XF3033/266 (P086) | 0° | 0.151 | 19/40 | m ≥ 0.05 dB/m |
Report XF3033/R3 Smoke Sensitivity Testing of Residential Smoke Alarms
| Sample | Orientation | Response Threshold Value (dB/m) | Ambient Air Temperature (°C) & Relative Humidity (%RH) | Requirement |
|---|---|---|---|---|
| XF3033/267 (P087) | 0° | 0.156 | 19/40 | m ≥ 0.05 dB/m |
| XF3033/268 (P088) | 0° | 0.146 | 19/40 | m ≥ 0.05 dB/m |
| XF3033/269 (P089) | 0° | 0.174 | 19/39 | m ≥ 0.05 dB/m |
| XF3033/270 (P090) | 0° | 0.168 | 19/39 | m ≥ 0.05 dB/m |
| XF3033/271 (P091) | 0° | 0.156 | 19/39 | m ≥ 0.05 dB/m |
| XF3033/272 (P092) | 0° | 0.156 | 22/36 | m ≥ 0.05 dB/m |
| XF3033/273 (P093) | 0° | 0.183 | 22/40 | m ≥ 0.05 dB/m |
| XF3033/274 (P094) | 0° | 0.169 | 22/36 | m ≥ 0.05 dB/m |
| XF3033/275 (P095) | 0° | 0.162 | 21/38 | m ≥ 0.05 dB/m |
| XF3033/276 (P096) | 0° | 0.140 | 21/38 | m ≥ 0.05 dB/m |
| XF3033/277 (P097) | 0° | 0.172 | 21/37 | m ≥ 0.05 dB/m |
| XF3033/278 (P098) | 0° | 0.147 | 21/37 | m ≥ 0.05 dB/m |
| XF3033/279 (P099) | 0° | 0.170 | 21/37 | m ≥ 0.05 dB/m |
| XF3033/280 (P100) | 0° | 0.165 | 21/37 | m ≥ 0.05 dB/m |
| XF3033/281 (P101) | 0° | 0.142 | 21/36 | m ≥ 0.05 dB/m |
| XF3033/282 (P102) | 0° | 0.160 | 21/36 | m ≥ 0.05 dB/m |
| XF3033/283 (P103) | 0° | 0.170 | 22/36 | m ≥ 0.05 dB/m |
| XF3033/284 (P104) | 0° | 0.153 | 21/36 | m ≥ 0.05 dB/m |
| XF3033/285 (P105) | 0° | 0.172 | 22/35 | m ≥ 0.05 dB/m |
| XF3033/286 (P106) | 0° | 0.165 | 22/35 | m ≥ 0.05 dB/m |
Report XF3033/R3 Smoke Sensitivity Testing of Residential Smoke Alarms
XF3033/287 (M061) through XF3033/332 (M106)
| Sample | Orientation | Response Threshold Value (dB/m) | Ambient Air Temperature (°C) & Relative Humidity (%RH) | Requirement |
|---|---|---|---|---|
| XF3033/287 (M061) | 315° | 0.167 | 23/39 | m ≥ 0.05 dB/m |
| XF3033/288 (M062) | 315° | 0.161 | 23/39 | m ≥ 0.05 dB/m |
| XF3033/289 (M063) | 315° | 0.167 | 23/39 | m ≥ 0.05 dB/m |
| XF3033/290 (M064) | 315° | 0.175 | 23/39 | m ≥ 0.05 dB/m |
| XF3033/291 (M065) | 315° | 0.158 | 23/39 | m ≥ 0.05 dB/m |
| XF3033/292 (M066) | 315° | 0.168 | 23/39 | m ≥ 0.05 dB/m |
| XF3033/293 (M067) | 315° | 0.171 | 23/39 | m ≥ 0.05 dB/m |
| XF3033/294 (M068) | 315° | 0.178 | 23/39 | m ≥ 0.05 dB/m |
| XF3033/295 (M069) | 315° | 0.158 | 24/38 | m ≥ 0.05 dB/m |
| XF3033/296 (M070) | 315° | 0.178 | 24/38 | m ≥ 0.05 dB/m |
| XF3033/297 (M071) | 315° | 0.172 | 24/38 | m ≥ 0.05 dB/m |
| XF3033/298 (M072) | 315° | 0.170 | 24/38 | m ≥ 0.05 dB/m |
| XF3033/299 (M073) | 315° | 0.170 | 23/38 | m ≥ 0.05 dB/m |
| XF3033/300 (M074) | 315° | 0.162 | 23/38 | m ≥ 0.05 dB/m |
| XF3033/301 (M075) | 315° | 0.177 | 23/38 | m ≥ 0.05 dB/m |
| XF3033/302 (M076) | 315° | 0.162 | 23/38 | m ≥ 0.05 dB/m |
| XF3033/303 (M077) | 315° | 0.164 | 23/38 | m ≥ 0.05 dB/m |
| XF3033/304 (M078) | 315° | 0.156 | 23/38 | m ≥ 0.05 dB/m |
| XF3033/305 (M079) | 315° | 0.166 | 23/38 | m ≥ 0.05 dB/m |
| XF3033/306 (M080) | 315° | 0.169 | 23/38 | m ≥ 0.05 dB/m |
| XF3033/307 (M081) | 315° | 0.180 | 23/38 | m ≥ 0.05 dB/m |
| XF3033/308 (M082) | 315° | 0.163 | 23/38 | m ≥ 0.05 dB/m |
| XF3033/309 (M083) | 315° | 0.191 | 23/38 | m ≥ 0.05 dB/m |
| XF3033/310 (M084) | 315° | 0.172 | 23/38 | m ≥ 0.05 dB/m |
| XF3033/311 (M085) | 315° | 0.170 | 24/38 | m ≥ 0.05 dB/m |
| XF3033/312 (M086) | 315° | 0.158 | 24/38 | m ≥ 0.05 dB/m |
Report XF3033/R3 Smoke Sensitivity Testing of Residential Smoke Alarms
| Sample | Orientation | Response Threshold Value (dB/m) | Ambient Air Temperature (°C) & Relative Humidity (%RH) | Requirement |
|---|---|---|---|---|
| XF3033/313 (M087) | 315° | 0.182 | 24/38 | m ≥ 0.05 dB/m |
| XF3033/314 (M088) | 315° | 0.187 | 24/38 | m ≥ 0.05 dB/m |
| XF3033/315 (M089) | 315° | 0.189 | 22/40 | m ≥ 0.05 dB/m |
| XF3033/316 (M090) | 315° | 0.180 | 24/38 | m ≥ 0.05 dB/m |
| XF3033/317 (M091) | 315° | 0.196 | 24/38 | m ≥ 0.05 dB/m |
| XF3033/318 (M092) | 315° | 0.166 | 22/40 | m ≥ 0.05 dB/m |
| XF3033/319 (M093) | 315° | 0.179 | 23/38 | m ≥ 0.05 dB/m |
| XF3033/320 (M094) | 315° | 0.175 | 23/38 | m ≥ 0.05 dB/m |
| XF3033/321 (M095) | 315° | 0.182 | 23/38 | m ≥ 0.05 dB/m |
| XF3033/322 (M096) | 315° | 0.173 | 23/38 | m ≥ 0.05 dB/m |
| XF3033/323 (M097) | 315° | 0.164 | 23/39 | m ≥ 0.05 dB/m |
| XF3033/324 (M098) | 315° | 0.167 | 23/39 | m ≥ 0.05 dB/m |
| XF3033/325 (M099) | 315° | 0.162 | 23/39 | m ≥ 0.05 dB/m |
| XF3033/326 (M100) | 315° | 0.186 | 23/39 | m ≥ 0.05 dB/m |
| XF3033/327 (M101) | 315° | 0.166 | 22/39 | m ≥ 0.05 dB/m |
| XF3033/328 (M102) | 315° | 0.155 | 22/39 | m ≥ 0.05 dB/m |
| XF3033/329 (M103) | 315° | 0.171 | 22/39 | m ≥ 0.05 dB/m |
| XF3033/330 (M104) | 315° | 0.171 | 22/39 | m ≥ 0.05 dB/m |
| XF3033/331 (M105) | 315° | 0.178 | 22/40 | m ≥ 0.05 dB/m |
| XF3033/332 (M106) | 315° | 0.173 | 22/40 | m ≥ 0.05 dB/m |
Report XF3033/R3 Smoke Sensitivity Testing of Residential Smoke Alarms
XF3033/333 (P107) through XF3033/356 (P130)
| Sample | Orientation | Response Threshold Value (dB/m) | Ambient Air Temperature (°C) & Relative Humidity (%RH) | Requirement |
|---|---|---|---|---|
| XF3033/333 (P107) | 135° | 0.092 | 19/50 | m ≥ 0.05 dB/m |
| XF3033/334 (P108) | 135° | 0.083 | 19/50 | m ≥ 0.05 dB/m |
| XF3033/335 (P109) | 135° | 0.091 | 18/49 | m ≥ 0.05 dB/m |
| XF3033/336 (P110) | 135° | 0.071 | 18/49 | m ≥ 0.05 dB/m |
| XF3033/337 (P111) | 135° | Permanent Alarm State | Not tested | m ≥ 0.05 dB/m |
| XF3033/338 (P112) | 135° | 0.068 | 19/51 | m ≥ 0.05 dB/m |
| XF3033/339 (P113) | 135° | 0.089 | 19/51 | m ≥ 0.05 dB/m |
| XF3033/340 (P114) | 135° | 0.088 | 18/51 | m ≥ 0.05 dB/m |
| XF3033/341 (P115) | 135° | 0.084 | 18/51 | m ≥ 0.05 dB/m |
| XF3033/342 (P116) | 135° | 0.090 | 19/52 | m ≥ 0.05 dB/m |
| XF3033/343 (P117) | 135° | 0.085 | 19/52 | m ≥ 0.05 dB/m |
| XF3033/344 (P118) | 135° | 0.086 | 19/52 | m ≥ 0.05 dB/m |
| XF3033/345 (P119) | 135° | 0.078 | 19/52 | m ≥ 0.05 dB/m |
| XF3033/346 (P120) | 135° | 0.077 | 19/52 | m ≥ 0.05 dB/m |
| XF3033/347 (P121) | 135° | 0.084 | 19/52 | m ≥ 0.05 dB/m |
| XF3033/348 (P122) | 135° | 0.086 | 19/52 | m ≥ 0.05 dB/m |
| XF3033/349 (P123) | 135° | 0.086 | 19/52 | m ≥ 0.05 dB/m |
| XF3033/350 (P124) | 135° | 0.068 | 19/52 | m ≥ 0.05 dB/m |
| XF3033/351 (P125) | 135° | 0.086 | 19/52 | m ≥ 0.05 dB/m |
| XF3033/352 (P126) | 135° | 0.090 | 19/52 | m ≥ 0.05 dB/m |
| XF3033/353 (P127) | 135° | 0.088 | 19/52 | m ≥ 0.05 dB/m |
| XF3033/354 (P128) | 135° | 0.081 | 19/53 | m ≥ 0.05 dB/m |
| XF3033/355 (P129) | 135° | 0.085 | 19/53 | m ≥ 0.05 dB/m |
| XF3033/356 (P130) | 135° | 0.086 | 19/53 | m ≥ 0.05 dB/m |
Report XF3033/R3 Smoke Sensitivity Testing of Residential Smoke Alarms
XF3033/357 (M107) through XF3033/380 (M130)
| Sample | Orientation | Response Threshold Value (dB/m) | Ambient Air Temperature (°C) & Relative Humidity (%RH) | Requirement |
|---|---|---|---|---|
| XF3033/357 (M107) | 180° | 0.080 | 24/54 | m ≥ 0.05 dB/m |
| XF3033/358 (M108) | 180° | 0.103 | 24/54 | m ≥ 0.05 dB/m |
| XF3033/359 (M109) | 180° | 0.113 | 24/54 | m ≥ 0.05 dB/m |
| XF3033/360 (M110) | 180° | 0.107 | 24/54 | m ≥ 0.05 dB/m |
| XF3033/361 (M111) | 180° | 0.090 | 24/53 | m ≥ 0.05 dB/m |
| XF3033/362 (M112) | 180° | 0.074 | 24/53 | m ≥ 0.05 dB/m |
| XF3033/363 (M113) | 180° | 0.100 | 24/53 | m ≥ 0.05 dB/m |
| XF3033/364 (M114) | 180° | 0.088 | 24/53 | m ≥ 0.05 dB/m |
| XF3033/365 (M115) | 180° | 0.091 | 24/51 | m ≥ 0.05 dB/m |
| XF3033/366 (M116) | 180° | 0.092 | 24/51 | m ≥ 0.05 dB/m |
| XF3033/367 (M117) | 180° | 0.093 | 24/51 | m ≥ 0.05 dB/m |
| XF3033/368 (M118) | 180° | 0.096 | 24/51 | m ≥ 0.05 dB/m |
| XF3033/369 (M119) | 180° | 0.096 | 24/51 | m ≥ 0.05 dB/m |
| XF3033/370 (M120) | 180° | 0.078 | 24/51 | m ≥ 0.05 dB/m |
| XF3033/371 (M121) | 180° | 0.089 | 24/51 | m ≥ 0.05 dB/m |
| XF3033/372 (M122) | 180° | 0.099 | 24/51 | m ≥ 0.05 dB/m |
| XF3033/373 (M123) | 180° | 0.130 | 24/50 | m ≥ 0.05 dB/m |
| XF3033/374 (M124) | 180° | 0.083 | 24/50 | m ≥ 0.05 dB/m |
| XF3033/375 (M125) | 180° | 0.131 | 24/50 | m ≥ 0.05 dB/m |
| XF3033/376 (M126) | 180° | 0.092 | 24/50 | m ≥ 0.05 dB/m |
| XF3033/377 (M127) | 180° | 0.084 | 24/49 | m ≥ 0.05 dB/m |
| XF3033/378 (M128) | 180° | 0.074 | 24/49 | m ≥ 0.05 dB/m |
| XF3033/379 (M129) | 180° | 0.092 | 24/49 | m ≥ 0.05 dB/m |
| XF3033/380 (M130) | 180° | 0.088 | 24/49 | m ≥ 0.05 dB/m |
Report XF3033/R3 Smoke Sensitivity Testing of Residential Smoke Alarms
XF3033/381 (D061) through XF3033/452 (D132)
| Sample | Orientation | Response Threshold Value (dB/m) | Ambient Air Temperature (°C) & Relative Humidity (%RH) | Requirement |
|---|---|---|---|---|
| XF3033/381 (D061) | 0° | 0.080 | 22/52 | m ≥ 0.05 dB/m |
| XF3033/382 (D062) | 0° | 0.072 | 22/52 | m ≥ 0.05 dB/m |
| XF3033/383 (D063) | 0° | 0.071 | 22/52 | m ≥ 0.05 dB/m |
| XF3033/384 (D064) | 0° | 0.064 | 22/52 | m ≥ 0.05 dB/m |
| XF3033/385 (D065) | 0° | 0.083 | 22/53 | m ≥ 0.05 dB/m |
| XF3033/386 (D066) | 0° | 0.069 | 22/53 | m ≥ 0.05 dB/m |
| XF3033/387 (D067) | 0° | 0.058 | 22/53 | m ≥ 0.05 dB/m |
| XF3033/388 (D068) | 0° | 0.059 | 22/53 | m ≥ 0.05 dB/m |
| XF3033/389 (D069) | 0° | 0.096 | 22/53 | m ≥ 0.05 dB/m |
| XF3033/390 (D070) | 0° | 0.073 | 22/53 | m ≥ 0.05 dB/m |
| XF3033/391 (D071) | 0° | 0.071 | 22/53 | m ≥ 0.05 dB/m |
| XF3033/392 (D072) | 0° | 0.069 | 22/53 | m ≥ 0.05 dB/m |
| XF3033/393 (D073) | 0° | 0.078 | 22/53 | m ≥ 0.05 dB/m |
| XF3033/394 (D074) | 0° | 0.074 | 22/53 | m ≥ 0.05 dB/m |
| XF3033/395 (D075) | 0° | 0.074 | 22/53 | m ≥ 0.05 dB/m |
| XF3033/396 (D076) | 0° | 0.088 | 22/53 | m ≥ 0.05 dB/m |
| XF3033/397 (D077) | 0° | 0.096 | 22/53 | m ≥ 0.05 dB/m |
| XF3033/398 (D078) | 0° | 0.057 | 22/53 | m ≥ 0.05 dB/m |
| XF3033/399 (D079) | 0° | 0.068 | 22/53 | m ≥ 0.05 dB/m |
| XF3033/400 (D080) | 0° | 0.070 | 22/53 | m ≥ 0.05 dB/m |
| XF3033/401 (D081) | 0° | 0.128 | 23/52 | m ≥ 0.05 dB/m |
| XF3033/402 (D082) | 0° | 0.076 | 23/52 | m ≥ 0.05 dB/m |
| XF3033/403 (D083) | 0° | 0.089 | 23/52 | m ≥ 0.05 dB/m |
| XF3033/404 (D084) | 0° | 0.098 | 23/52 | m ≥ 0.05 dB/m |
| XF3033/405 (D085) | 0° | 0.070 | 23/50 | m ≥ 0.05 dB/m |
| XF3033/406 (D086) | 0° | 0.059 | 23/50 | m ≥ 0.05 dB/m |
| XF3033/407 (D087) | 0° | 0.079 | 23/50 | m ≥ 0.05 dB/m |
Report XF3033/R3 Smoke Sensitivity Testing of Residential Smoke Alarms
| Sample | Orientation | Response Threshold Value (dB/m) | Ambient Air Temperature (°C) & Relative Humidity (%RH) | Requirement |
|---|---|---|---|---|
| XF3033/408 (D088) | 0° | 0.096 | 23/50 | m ≥ 0.05 dB/m |
| XF3033/409 (D089) | 0° | 0.071 | 23/49 | m ≥ 0.05 dB/m |
| XF3033/410 (D090) | 0° | 0.078 | 23/49 | m ≥ 0.05 dB/m |
| XF3033/411 (D091) | 0° | 0.095 | 23/49 | m ≥ 0.05 dB/m |
| XF3033/412 (D092) | 0° | 0.070 | 23/49 | m ≥ 0.05 dB/m |
| XF3033/413 (D093) | 0° | 0.089 | 23/49 | m ≥ 0.05 dB/m |
| XF3033/414 (D094) | 0° | 0.068 | 23/49 | m ≥ 0.05 dB/m |
| XF3033/415 (D095) | 0° | 0.072 | 23/49 | m ≥ 0.05 dB/m |
| XF3033/416 (D096) | 0° | 0.089 | 23/49 | m ≥ 0.05 dB/m |
| XF3033/417 (D097) | 0° | 0.084 | 23/48 | m ≥ 0.05 dB/m |
| XF3033/418 (D098) | 0° | 0.066 | 23/48 | m ≥ 0.05 dB/m |
| XF3033/419 (D099) | 0° | 0.061 | 23/48 | m ≥ 0.05 dB/m |
| XF3033/420 (D100) | 0° | 0.078 | 23/48 | m ≥ 0.05 dB/m |
| XF3033/421 (D101) | 0° | 0.084 | 23/44 | m ≥ 0.05 dB/m |
| XF3033/422 (D102) | 0° | 0.080 | 23/44 | m ≥ 0.05 dB/m |
| XF3033/423 (D103) | 0° | 0.075 | 23/44 | m ≥ 0.05 dB/m |
| XF3033/424 (D104) | 0° | 0.078 | 23/44 | m ≥ 0.05 dB/m |
| XF3033/425 (D105) | 0° | 0.088 | 22/45 | m ≥ 0.05 dB/m |
| XF3033/426 (D106) | 0° | 0.061 | 22/45 | m ≥ 0.05 dB/m |
| XF3033/427 (D107) | 0° | 0.096 | 22/45 | m ≥ 0.05 dB/m |
| XF3033/428 (D108) | 0° | 0.092 | 22/45 | m ≥ 0.05 dB/m |
| XF3033/429 (D109) | 0° | 0.081 | 22/44 | m ≥ 0.05 dB/m |
| XF3033/430 (D110) | 0° | 0.069 | 22/44 | m ≥ 0.05 dB/m |
| XF3033/431 (D111) | 0° | 0.062 | 22/44 | m ≥ 0.05 dB/m |
| XF3033/432 (D112) | 0° | 0.064 | 22/44 | m ≥ 0.05 dB/m |
| XF3033/433 (D113) | 0° | 0.058 | 22/45 | m ≥ 0.05 dB/m |
| XF3033/434 (D114) | 0° | 0.064 | 22/45 | m ≥ 0.05 dB/m |
| XF3033/435 (D115) | 0° | 0.071 | 22/45 | m ≥ 0.05 dB/m |
Report XF3033/R3 Smoke Sensitivity Testing of Residential Smoke Alarms
| Sample | Orientation | Response Threshold Value (dB/m) | Ambient Air Temperature (°C) & Relative Humidity (%RH) | Requirement |
|---|---|---|---|---|
| XF3033/436 (D116) | 0° | 0.073 | 22/45 | m ≥ 0.05 dB/m |
| XF3033/437 (D117) | 0° | 0.066 | 22/44 | m ≥ 0.05 dB/m |
| XF3033/438 (D118) | 0° | 0.096 | 22/44 | m ≥ 0.05 dB/m |
| XF3033/439 (D119) | 0° | 0.076 | 22/44 | m ≥ 0.05 dB/m |
| XF3033/440 (D120) | 0° | 0.057 | 22/44 | m ≥ 0.05 dB/m |
| XF3033/441 (D121) | 0° | 0.102 | 22/44 | m ≥ 0.05 dB/m |
| XF3033/442 (D122) | 0° | 0.074 | 22/44 | m ≥ 0.05 dB/m |
| XF3033/443 (D123) | 0° | 0.080 | 22/44 | m ≥ 0.05 dB/m |
| XF3033/444 (D124) | 0° | 0.087 | 22/44 | m ≥ 0.05 dB/m |
| XF3033/445 (D125) | 0° | 0.071 | 22/43 | m ≥ 0.05 dB/m |
| XF3033/446 (D126) | 0° | 0.062 | 22/43 | m ≥ 0.05 dB/m |
| XF3033/447 (D127) | 0° | 0.074 | 22/43 | m ≥ 0.05 dB/m |
| XF3033/448 (D128) | 0° | 0.073 | 22/43 | m ≥ 0.05 dB/m |
| XF3033/449 (D129) | 0° | 0.070 | 22/42 | m ≥ 0.05 dB/m |
| XF3033/450 (D130) | 0° | 0.068 | 22/42 | m ≥ 0.05 dB/m |
| XF3033/451 (D131) | 0° | 0.086 | 22/42 | m ≥ 0.05 dB/m |
| XF3033/452 (D132) | 0° | 0.083 | 22/42 | m ≥ 0.05 dB/m |
Report XF3033/R3 Smoke Sensitivity Testing of Residential Smoke Alarms
XF3033/453 (I061) through XF3033/524 (I132)
| Sample | Orientation | Response Threshold Value (MIC y) | Ambient Air Temperature (°C) & Relative Humidity (%RH) | Requirement |
|---|---|---|---|---|
| XF3033/453 (I061) | 0° | 0.85 | 22/40 | 0.05 ≤ Δy/Δt ≤ 0.3 |
| XF3033/454 (I062) | 0° | 0.70 | 22/40 | 0.05 ≤ Δy/Δt ≤ 0.3 |
| XF3033/455 (I063) | 0° | 0.79 | 22/40 | 0.05 ≤ Δy/Δt ≤ 0.3 |
| XF3033/456 (I064) | 0° | 0.74 | 22/40 | 0.05 ≤ Δy/Δt ≤ 0.3 |
| XF3033/457 (I065) | 0° | 0.80 | 21/40 | 0.05 ≤ Δy/Δt ≤ 0.3 |
| XF3033/458 (I066) | 0° | 0.71 | 21/40 | 0.05 ≤ Δy/Δt ≤ 0.3 |
| XF3033/459 (I067) | 0° | 0.85 | 21/40 | 0.05 ≤ Δy/Δt ≤ 0.3 |
| XF3033/460 (I068) | 0° | 0.71 | 21/40 | 0.05 ≤ Δy/Δt ≤ 0.3 |
| XF3033/461 (I069) | 0° | 0.84 | 21/40 | 0.05 ≤ Δy/Δt ≤ 0.3 |
| XF3033/462 (I070) | 0° | 0.70 | 21/40 | 0.05 ≤ Δy/Δt ≤ 0.3 |
| XF3033/463 (I071) | 0° | 0.78 | 21/40 | 0.05 ≤ Δy/Δt ≤ 0.3 |
| XF3033/464 (I072) | 0° | 0.82 | 21/40 | 0.05 ≤ Δy/Δt ≤ 0.3 |
| XF3033/465 (I073) | 0° | 0.76 | 21/39 | 0.05 ≤ Δy/Δt ≤ 0.3 |
| XF3033/466 (I074) | 0° | 0.78 | 21/39 | 0.05 ≤ Δy/Δt ≤ 0.3 |
| XF3033/467 (I075) | 0° | 0.90 | 21/39 | 0.05 ≤ Δy/Δt ≤ 0.3 |
| XF3033/468 (I076) | 0° | 0.75 | 21/39 | 0.05 ≤ Δy/Δt ≤ 0.3 |
| XF3033/469 (I077) | 0° | 0.86 | 23/40 | 0.05 ≤ Δy/Δt ≤ 0.3 |
| XF3033/470 (I078) | 0° | 0.68 | 23/40 | 0.05 ≤ Δy/Δt ≤ 0.3 |
| XF3033/471 (I079) | 0° | 0.72 | 23/40 | 0.05 ≤ Δy/Δt ≤ 0.3 |
| XF3033/472 (I080) | 0° | 0.78 | 23/40 | 0.05 ≤ Δy/Δt ≤ 0.3 |
| XF3033/473 (I081) | 0° | 0.72 | 23/40 | 0.05 ≤ Δy/Δt ≤ 0.3 |
| XF3033/474 (I082) | 0° | 0.72 | 23/40 | 0.05 ≤ Δy/Δt ≤ 0.3 |
| XF3033/475 (I083) | 0° | 0.73 | 23/40 | 0.05 ≤ Δy/Δt ≤ 0.3 |
| XF3033/476 (I084) | 0° | 0.75 | 23/40 | 0.05 ≤ Δy/Δt ≤ 0.3 |
| XF3033/477 (I085) | 0° | 0.74 | 23/40 | 0.05 ≤ Δy/Δt ≤ 0.3 |
| XF3033/478 (I086) | 0° | 0.74 | 23/40 | 0.05 ≤ Δy/Δt ≤ 0.3 |
| XF3033/479 (I087) | 0° | 0.71 | 23/40 | 0.05 ≤ Δy/Δt ≤ 0.3 |
Report XF3033/R3 Smoke Sensitivity Testing of Residential Smoke Alarms
| Sample | Orientation | Response Threshold Value (MIC y) | Ambient Air Temperature (°C) & Relative Humidity (%RH) | Requirement |
|---|---|---|---|---|
| XF3033/480 (I088) | 0° | 0.74 | 23/40 | $0.05 \le \Delta y/\Delta t \le 0.3$ |
| XF3033/481 (I089) | 0° | 0.75 | 23/40 | $0.05 \le \Delta y/\Delta t \le 0.3$ |
| XF3033/482 (I090) | 0° | 0.78 | 23/40 | $0.05 \le \Delta y/\Delta t \le 0.3$ |
| XF3033/483 (I091) | 0° | 0.95 | 23/40 | $0.05 \le \Delta y/\Delta t \le 0.3$ |
| XF3033/484 (I092) | 0° | 0.83 | 23/40 | $0.05 \le \Delta y/\Delta t \le 0.3$ |
| XF3033/485 (I093) | 0° | 0.75 | 23/39 | $0.05 \le \Delta y/\Delta t \le 0.3$ |
| XF3033/486 (I094) | 0° | 0.80 | 23/39 | $0.05 \le \Delta y/\Delta t \le 0.3$ |
| XF3033/487 (I095) | 0° | 0.69 | 23/39 | $0.05 \le \Delta y/\Delta t \le 0.3$ |
| XF3033/488 (I096) | 0° | 0.68 | 23/39 | $0.05 \le \Delta y/\Delta t \le 0.3$ |
| XF3033/489 (I097) | 0° | 0.69 | 22/39 | $0.05 \le \Delta y/\Delta t \le 0.3$ |
| XF3033/490 (I098) | 0° | 0.71 | 22/39 | $0.05 \le \Delta y/\Delta t \le 0.3$ |
| XF3033/491 (I099) | 0° | 0.78 | 22/39 | $0.05 \le \Delta y/\Delta t \le 0.3$ |
| XF3033/492 (I100) | 0° | 0.72 | 22/39 | $0.05 \le \Delta y/\Delta t \le 0.3$ |
| XF3033/493 (I101) | 0° | 0.72 | 22/40 | $0.05 \le \Delta y/\Delta t \le 0.3$ |
| XF3033/494 (I102) | 0° | 0.68 | 22/40 | $0.05 \le \Delta y/\Delta t \le 0.3$ |
| XF3033/495 (I103) | 0° | 0.85 | 22/40 | $0.05 \le \Delta y/\Delta t \le 0.3$ |
| XF3033/496 (I104) | 0° | 0.65 | 22/40 | $0.05 \le \Delta y/\Delta t \le 0.3$ |
| XF3033/497 (I105) | 0° | 0.85 | 22/40 | $0.05 \le \Delta y/\Delta t \le 0.3$ |
| XF3033/498 (I106) | 0° | 0.72 | 22/40 | $0.05 \le \Delta y/\Delta t \le 0.3$ |
| XF3033/499 (I107) | 0° | 0.71 | 22/40 | $0.05 \le \Delta y/\Delta t \le 0.3$ |
| XF3033/500 (I108) | 0° | 0.79 | 22/40 | $0.05 \le \Delta y/\Delta t \le 0.3$ |
| XF3033/501 (I109) | 0° | 0.71 | 22/40 | $0.05 \le \Delta y/\Delta t \le 0.3$ |
| XF3033/502 (I110) | 0° | 0.71 | 22/40 | $0.05 \le \Delta y/\Delta t \le 0.3$ |
| XF3033/503 (I111) | 0° | 0.78 | 22/40 | $0.05 \le \Delta y/\Delta t \le 0.3$ |
| XF3033/504 (I112) | 0° | 0.87 | 22/40 | $0.05 \le \Delta y/\Delta t \le 0.3$ |
| XF3033/505 (I113) | 0° | 0.75 | 22/40 | $0.05 \le \Delta y/\Delta t \le 0.3$ |
| XF3033/506 (I114) | 0° | 0.78 | 22/40 | $0.05 \le \Delta y/\Delta t \le 0.3$ |
| XF3033/507 (I115) | 0° | 0.74 | 22/40 | $0.05 \le \Delta y/\Delta t \le 0.3$ |
Report XF3033/R3 Smoke Sensitivity Testing of Residential Smoke Alarms
| Sample | Orientation | Response Threshold Value (MIC y) | Ambient Air Temperature (°C) & Relative Humidity (%RH) | Requirement |
|---|---|---|---|---|
| XF3033/508 (I116) | 0° | 0.74 | 22/40 | 0.05 ≤ Δy/Δt ≤ 0.3 |
| XF3033/509 (I117) | 0° | 0.85 | 22/40 | 0.05 ≤ Δy/Δt ≤ 0.3 |
| XF3033/510 (I118) | 0° | 0.77 | 22/40 | 0.05 ≤ Δy/Δt ≤ 0.3 |
| XF3033/511 (I119) | 0° | 0.85 | 22/40 | 0.05 ≤ Δy/Δt ≤ 0.3 |
| XF3033/512 (I120) | 0° | 0.77 | 22/40 | 0.05 ≤ Δy/Δt ≤ 0.3 |
| XF3033/513 (I121) | 0° | 0.84 | 21/40 | 0.05 ≤ Δy/Δt ≤ 0.3 |
| XF3033/514 (I122) | 0° | 0.75 | 21/40 | 0.05 ≤ Δy/Δt ≤ 0.3 |
| XF3033/515 (I123) | 0° | 0.71 | 21/40 | 0.05 ≤ Δy/Δt ≤ 0.3 |
| XF3033/516 (I124) | 0° | 0.71 | 21/40 | 0.05 ≤ Δy/Δt ≤ 0.3 |
| XF3033/517 (I125) | 0° | 0.68 | 21/40 | 0.05 ≤ Δy/Δt ≤ 0.3 |
| XF3033/518 (I126) | 0° | 0.78 | 21/40 | 0.05 ≤ Δy/Δt ≤ 0.3 |
| XF3033/519 (I127) | 0° | 0.69 | 21/40 | 0.05 ≤ Δy/Δt ≤ 0.3 |
| XF3033/520 (I128) | 0° | 0.81 | 21/40 | 0.05 ≤ Δy/Δt ≤ 0.3 |
| XF3033/521 (I129) | 0° | 0.76 | 21/40 | 0.05 ≤ Δy/Δt ≤ 0.3 |
| XF3033/522 (I130) | 0° | 0.76 | 21/40 | 0.05 ≤ Δy/Δt ≤ 0.3 |
| XF3033/523 (I131) | 0° | 0.87 | 21/40 | 0.05 ≤ Δy/Δt ≤ 0.3 |
| XF3033/524 (I132) | 0° | 0.67 | 21/40 | 0.05 ≤ Δy/Δt ≤ 0.3 |
Report XF3033/R3 Smoke Sensitivity Testing of Residential Smoke Alarms
4 REFERENCE INFORMATION
The following information is provided to assist in the interpreting of the results detailed in this report.
4.1 Obscuration vs. Ionisation data
The data shown in Figure 3 demonstrates the relationship between smoke density measured by the reference IR obscurometer (measured in dB/m) and by the reference measuring ionisation chamber (MIC, measured in terms of “MIC y”). Refer to Section C2 of AS 3786:2014 for details of the MIC and its response values.
〔图〕插图
Figure 3. Typical response values of the reference obscuometer and MIC, as fitted to the CSIRO AS 3786 / AS 7240.7 test tunnel, to aspirated paraffin during tunnel sensitivity tests of smoke alarms and detectors.
4.2 Obscuration units
The data shown in Figure 4 and Figure 5 demonstrates the relationship between smoke density calculated in terms of the units of dB/m and %obscuration/m.
Report XF3033/R3 Smoke Sensitivity Testing of Residential Smoke Alarms
〔图〕插图
Figure 4. Relationship between smoke density as measured in dB/m and %obs/m to 10 %obs/m.
〔图〕插图