NATIONAL

分类:06_境外及港澳台调查报告 / 1980/美国_NTSB 年份:1980 大小:70.9 KB 知识库创建:2026-08-05 09:00:48 抓取时间:2026-10-22 09:04:50

8 PE81-15697U

〔图〕、\n 〔图〕插图

NATIONAL

TRANSPORTATION SAFETY BOARD

WASHINGTON, D.C. 20594

〔图〕插图

PIPELINE ACCIDENT REPORTS

BRIEF FORMAT ISSUE NUMBER 1 - 1980

〔图〕插图 NTSB-PAB-80-1

〔图〕插图 UNITED STATES GOVERNMENT

REPRODUCED BY NATIONAL TECHNICAL INFORMATION SERVICE U.S. DEPARTMENT OF COMGERCE SPRINGFIELD, VA 22163

TECHNICAL REPORT DOCUMENTATION PAGE

1. Report No.2. Government Accession No.3. Recipient's Fataling No. P. 156978
NTSR-PAR-80-1NTSR-PAR-80-1NTSR-PAR-80-1
4. Title and SubtitlePipeline Accident Reports -- Brief Format, Issue #1 - 19802. Government Accession No.5. Report DateSeptember 18, 1980
4. Title and SubtitlePipeline Accident Reports -- Brief Format, Issue #1 - 19802. Government Accession No.6. Performing Organization Code
7. Author(s)7. Author(s)8. Performing Organization Report No.
9. Performing Organization Name and AddressNational Transportation Safety Board Bureau of Accident Investigation Washington, D.C. 2059410. Work Unit No.3049
9. Performing Organization Name and AddressNational Transportation Safety Board Bureau of Accident Investigation Washington, D.C. 2059411. Contract or Grant No.
9. Performing Organization Name and AddressNational Transportation Safety Board Bureau of Accident Investigation Washington, D.C. 2059413. Type of Report and Period Covered42 U.S. Pipeline Accidents occurring in 1976, 1977, 1978, and 1979 in Brief Format.
12. Sponsoring Agency Name and AddressNATIONAL TRANSPORTATION SAFETY BOARD Washington, D. C. 2059413. Type of Report and Period Covered42 U.S. Pipeline Accidents occurring in 1976, 1977, 1978, and 1979 in Brief Format.
12. Sponsoring Agency Name and AddressNATIONAL TRANSPORTATION SAFETY BOARD Washington, D. C. 2059414. Sponsoring Agency Code
This publication contains briefs of selected pipeline accidents, occurring during the calendar years 1976, 1977, 1978, and 1979. The brief format presents basic facts, conditions, and probable cause(s) in each instance.
File Numbers:DCA-76-FP-021 DCA-77-FP-023 DCA-78-FP-001 FTW-79-FP-002 DCA-80-FP-002DCA-77-FP-025 FTW-78-FP-001 FTW-79-FP-003 FTW-80-FP-002LAX-78-FP-001 FTW-79-FP-004 DCA-80-FP-006DCA-78-FP-002 FTW-79-FP-005FTW-78-FP-002 FTW-79-FP-006DCA-79-FP-007DCA-78-FP-004 FTW-79-FP-007FTW-78-FP-004 FTW-79-FP-009DCA-78-FP-006 FTW-79-FP-011FTW-78-FP-007 FTW-79-FP-012DCA-78-FP-009 FTW-79-FP-014FTW-78-DP-010 DCA-79-FP-017FTW-78-FP-012 DCA-79-FP-020FTW-78-FP-013 DCA-79-FP-022FTW-78-FP-014
17. Key Words External corrosion, improper operating procedure, outside force damage, rapidly expanding circumferential fracture, material failure, hydrogen stress cracking, inadequate control devices, soil movement, excavation damage, customer's service line, LPG gas, live abandoned service line gas compressor station18. Distribution StatementThis document is available to the public through the National Technical Information Service, Speingfield, Virginia 22161.
19. Security Classification (of this report)UNCLASSIFIED20. Security Classification (of this page)UNCLASSIFIED21. No. of Pages 22. Price

WTSB Form 1765.2 (Rev. 9/74)

i

FOREWORD

The National Transportation Safety Board, in accordance with the provisions of the Independent Safety Board Act of 1974, has determined the probable cause of the accidents reported herein.

This publication contains the reports of 42 pipeline accidents arranged in chronological order.

The enclosed briefs are the reports of the National Transportation Safety Board and are thereby subject to the limitations of 49 USC 1903(c):

"No part of any report or reports of the Board, relating to any accident or the investigation thereof, shall be admitted as evidence or used in any suit or action for damages growing out of any matter mentioned in such report or reports."

For those readers who wish more detailed information, the original factual reports are on file in the Washington, D.C. office of the National Transportation Safety Board and may be examined. These reports will be reproduced for a fee covering reproduction costs and postage. Orders for materials are also subject to a user charge by the Board for special services, and such charges will be included in the bill.

National Transportation Safety Board Public Inquiries Section Washington, D.C. 20594

TABLE OF CONTENTS

PAGE

FOREWORD $\ldots$ 11

TABLE OF CONTENTS $\ldots$ 111

EXPLANATORY NOTES 1

ALPHABETICAL LIST OF ACCIDENTS $\ldots$ 3

REPORTS OF ACCIDENTS 6

-1-

EXPLANATORY NOTES

Scope

The accidents included herein are those occurrences incidental to pipeline operations which fall within the scope of Section 304 of the Independent Safety Board Act of 1974. As provided in this Section the Board shall investigate and determine facts, conditions, circumstances, and the probable cause of any pipeline accident in which there is a fatality, or substantial property damage.

The following definitions have been established by the Safety Board in implementing the Independent Safety Board Act of 1974 (49 USC 1901):

Fatality

"Fatality" means the death of a person either at the time a pipeline accident occurs or within 60 days thereafter.

Substantial Damage

"Substantial damage" means damage of $100,000 or more to pipeline and non-pipeline property.

The following definitions, as set forth in Title 49 of the Code of Federal Regulations, Parts 192 and 195, are applicable:

49 CFR 192.3

Gas

"Gas" means natural gas, flammable gas, or gas which is toxic or corrosive.

Main

"Main" means a distribution line that serves as a common source of supply for more than one service line.

Service Line

"Service line" means a distribution line that transports gas from a common source of supply to (a) a customer meter or the connection to a customer's piping, whichever is farther downstream, or (b) the connection to a customer's piping if there is no customer meter. A customer meter is the meter that measures the transfer of gas from an operator to a consumer.

· 2 -

Transmission Line

"Transmission line" means a pipeline, other than a gathering line, that:

(a) Transports gas from a gathering line or storage facility to a distribution center or storage facility;

(b) Operates at a hoop stress of 20 percent or more of SMYS: or

(c) Transports gas within a storage field.

Transportation of Gas

"Transportation of Gas" means the gathering, transmission, or distribution of gas by pipeline or the storage of gas, in or affecting interstate or foreign commerce.

Pipeline

"Pipeline" means all parts of those physical facilities through which gas moves in transportation, including pipe, valves, and other appurtenance attached to pipe, compressor units, metering stations, regulator stations, delivery stations, holders, and fabricated assemblies.

Pipeline Facility

"Pipeline facility" means new and existing pipelines, right-of-way, and any equipment, facility, or building used in the transportation of gas or in the treatment of gas during the course of transportation.

49 CFR 195.2

Liquid

"Commodity" means a hazardous material that is subject to Parts 172 and 173 of this chapter, petroleum, and petroleum products.

Pipeline System

"Pipeline system" or "pipeline" means all parts of a carrier's physical facilities through which commodities move in transportation that is subject to this part, including, but not limited to line pipe, valves and other appurtenances connected to line pipe, pumping units, fabricated assemblies associated with pumping units, metering and delivery stations and fabricated assemblies therein and carrier-controlled breakout tankage.

-3-

Alphabetical List of Accidents

LocationCompanyDatePage
Albuquerque, New MexicoGas Company of New Mexico7/25/796
Arlington, TexasLone Star Gas Co.5/29/787
Arlington, TexasLone Star Gas Co.11/27/788
Auburn, AlabamaAlabama Gas Corp.1/15/789
Baltimore, MarylandBaltimore Gas and Electric6/6/7910
Berwick, LouisianaTexas Pipeline Co.1/2/8011
Chicago, IllinoisPeople's Gas Light and Coke Company10/14/7712
Chrisman, IllinoisCentral Illinois Light Company10/13/7913
Conway, KansasHydrocarbon Transportation Inc. (HTI)1/12/7814
Enid, OklahomaChamplin Petroleum Co.8/13/7915
Fort Payne, AlabamaDekalk-Cherokee Natural Gas District11/17/7916
Grand Island, NebraskaNorthwestern Public Service Company8/28/7817
Greenville, North CarolinaCarson Gas Company6/28/7718
Hamden, ConnecticutSouthern Connecticut Natural Gas Co.10/18/7719
Hastings, NebraskaHastings Utilities2/10/7920
Indianapolis, IndianaCitizens Gas and Coke Utility5/5/7721
Irving, TexasLone Star Gas Co.1/11/7922
Lafayette, LouisianaCentral Louisiana Electric Co., Inc.8/7/7823
LocationCompanyDatePage
Lewisburg, TennesseeLewisburg Gas Department (Municipal)10/31/7624
Lincoln, NebraskaCENGAS Div. of Minnesota Gas Co.11/9/7725
Mountain View, CaliforniaPacific Gas & Electric Co.4/19/7926
Nebraska City, NebraakaNebraska City Utilities9/1/7827
New Orleans, LouisianaNew Orleans Public Service2/7/7828
North Richland Hills, TexasLone Star Gas Co.1/19/7929
Orange, TexasCities Service Pipeline Company8/20/7930
Padre Island, TexasFlorida Gas Transmission Company1/27/7831
Pearland, TexasUnited Texas Transmission Co.10/24/7832
Phoenix, ArizonaArizona Public Service Company6/30/7833
Pierre Part, LouisianaDow Chemical USA9/4/7934
Pittsburgh, PennsylvaniaThe Peoples Natural Gas Company7/31/7935
Roswell, GeorgiaAtlanta Gas Light Company7/25/7936
Royal Oak, MichiganConsumers Power Company1/16/7937
Seat Pleasant, MarylandWashington Gas Light Company8/15/7938
Shreveport, LouisianaArkansas-Louisiana Gas Company10/30/7739
Slapout, OklahomaDelhi Gas Pipeline Corporation5/25/7940

-5-

LocationCompanyDatePage
Snowmass Village, ColoradoRocky Moutain Natural Gas Co.3/30/7941
Sterling City, TexasMid America Pipeline System11/8/7942
Stoughton, MassachusettsBay State Gas Company1/25/7843
Sullivan, IndianaOhio Valley Gas Corp.2/10/7844
Tempe, ArizonaArizona Public Service Company12/10/7745
Weimar, TexasLoVace Gathering Co.4/7/7846
West Lafayette, IndianaIndiana Gas Co., Inc.11/24/7747

NATIONAL TRANSPORTATION SAFETY BOARD WASHINGTON, D.C. 20594 Brief of Accident

FTW-79-F-PØ11

Pipeline Accident:

PY 79, Qtr. 4th

CompanyTypeComodityDateLocation
Gas Company of New MexicoGas DistributionNatural Gas7-25-79Albuquerque, New Mexico

Accident: At 5:51 p.m., m.d.t., on July 25, 1979, natural gas at 38 psig pressure escaping from a separation in a service line found at a 1-inch dresser coupling located underneath one of the apartments of a duplex house, accumulated, exploded, and ignited. Ignition occurred when one of the occupants struck a match to light a stove. The 3/4-inch steel mill-wrapped pipe was bent severely by a telephone company backhoe while working in the street to locate a telephone cable. The backhoe operator did not await the marking of the service line and did not know that the natural gas line was there until the excavation equipment hit it. The service line changed to 1-inch at the inlet side of the coupling and a 2-inch separation existed between the coupling and the pipe which indicated that the pipe had been pulled out. Two persons were killed, two persons were hospitalized for burns, the duplex apartment house was destroyed, and adjacent houses were damaged. The odor of gas was detected by residents but not reported.

LOSSES: by residents but not reported. Fatalities 2 Reportable Injuries 2 ; Pipeline Damage $ 1,800 Non-Pipeline Damage $ 30,000

Probable Causes: 1. Pipeline damaged by backhoe.

  1. Excavator unaware that he had damaged pipeline.
  1. Failure of excavator to wait for marking of pipeline location.
  1. Failure of residents to report gas odor.

Other Factors: 1.

Probable Cause of Casualties:

  1. Fatalities due to burns and collapse of structure as a result of primary loss event.
  1. Injuries due to burns and collapse of structure as a result of primary loss event.

Other Casualty Factors:

Recomendations: None

NATIONAL TRANSPORTATION SAFETY BOARD

WASHINGTON, D.C. 20594

Brief of Accident

FTW-78-F-PQ-19

Company Lone Star Gas Co.

Pipeline Accident: FY 78, Qtr. 3rd

CommodityDateLocation
Natural Gas5-29-78Arlington, Texas

Accident: At 8:45 a.m., c.d.t., on May 29, 1978, natural gas leaking from two corrosion holes in a 1-inch bare steel gas customer yard line operating at a pressure of 11 psig and covered by 17 inches of soil which had been saturated by heavy rains the day before, migrated beneath a house resting on a pier and beam foundation. And was ignited by the pilot light on a gas hot water. The resulting explosion destroyed the one-story brick house and damaged adjacent houses. There were no fatalities or injuries. The bare yard line was part of an unprotected gas piping system leading from the outlet side of the curb valve to the inlet side of the customer's meter. The operator's service line was a coated and wrapped steel pipe connected to the main with an insulated coupling. There was no apparent insulated fitting between the fuel line and the uncoated yard line. As a result the yard line was anodic to the house piping, part of which was burned, and galvanic corrosion resulted. Pipeline Non-Pipeline

LOSSES: Fatalities - ; Reportable Injuries - ; Damage $ ______ Damage $ 100,000

Probable Causes: 1. Corrosion due to lack of cathodic protection.

Other Factors: 1. Improper/inadequate procedures for design, installation and inspection of gas service lines.

Probable Cause of Casualties: 1.

Other Casualty Factors: 1.

Recommendations: R-79-32 & 33

NATIONAL TRANSPORTATION SAFETY BOARD

WASHINGTON, D.C. 20594

Brief of Accident

FTW-79-F-PØØ2

Pipeline Accident: FY_79, Qtr. 1st

CompanyTypeCommodityDateLocation
Lone Star Gas Co.Gas DistributionNatural Gas11/27/78Arlington, Texas

Accident: At 7:45 a.m., c.s.t., on November 27, 1978, natural gas leaking from a circumferential fracture in a threaded, 1-inch steel nipple - part of the "swing connection," off the tap on a service line - operating at a pressure of 14 psig, migrated laterally along the gas main and water line beneath and into the house where it was ignited when an electric heater was turned off. An explosion and flash fire resulted, with the fire fatally injuring one occupant and seriously injuring the other. The house suffered extensive damage from the explosion and some fire damage.

LOSSES: Fatalities 1; Reportable Injuries 1; Pipeline Damage · 1,000 Non-Pipeline Damage · 15,000

Probable Causes: 1. Earth side/movement, moisture related causing direct damage to pipeline.

Other Factors: 1.

Probable Cause of Casualties: 1. Fatality and injury due to fire as direct result of primary loss event.

Other Casualty Factore: 1.

Recommendations: P-79-27, P-79-28

NATIONAL TRANSPORTATION SAFETY BOARD WASHINGTON, D.C. 20594 Brief of Accident

DCA-73-F-P 69-73

Pipeline Accident:

FY 78, Qtr. 2nd

Company

type

Comodity

Date

Location

Alabama Gas Corporation

Distribution

Natural Gas

Auburn, Alabama

(ALAGASCO)

Accident: Natural gas escaped froz a circumferential break in a 3-inch cast-iron main located at a depth of 18 inches and operating at a pressure of 22 psig. An overlying sidewalk contained upward movement of the gas and part of it migrated laterally into the basement of a nearby building. Ignition of the gas was probably provided by a floor furnace, as indicated by its position relative to the damage in the basement and by the unusual explosive force which would have resulted from a high concentration of natural gas in the basement triggered when the lower explosive limit was reached in the floor furnace. This explosion and fire destroyed several commercial buildings and damaged over 50 other buildings. Metallurgical examination revealed that graphitization had weakened the pipe.

LOSSES: Patalities 0; Reportable Injuries 0; Pipeline Damage $ 56,000 Non-Pipeline Damage $ 1,500,000

Probable Causes: 1. Material failure of cast-iron pipe due to graphitization which weakened material. 2.

Other Factors: 1. Environment - temperature change.

2. Traffic vibration.

(Stresses which may have fractured weakened cast-iron pipe.)

Probable Cause of Casualties: 1.

Other: Casualty Factors:

Recommendations: None

NATIONAL TRANSPOKTATION SAFETY BOARD WASHINGTON, D.C. 20594 Brief of Accident

DCA-79-FP-Ø17

Pipeline Accident:

PX 79 , Qtr. 2nd

CompanyTypeCommodityDateLocation
Baltimore Gas andDistributionNatural Gas06/06/79Baltimore, Maryland
Electric

Accident: A contractor, while excavating for a subway station, struck a new 1 1/4-inch steel coated service line operating at 7 inches of water column (7" W.C.). The impact of the heavy equipment (backhoe bucket) upon the 12-foot-long service line caused it to bend. The force of the impact pulled the elbow, which connected the service line to the indoor meter river, approximately 52 inches into the brick wall. The break occurred on the pipe near the elbow. Natural gas escaped from the broken service line and migrated into the basement of the three buildings and ignited from an unknown source. The explosion and firefully demolished three, three-story buildings, and severely damaged adjacent buildings. The service line locations in the area were visibly marked on the buildings walls with wide lines of yellow paint.

LOSSES: Fatalities 0 Reportable Injuries 0 Damage $596.00 Damage $120.000.00

Probable Causes: 1. Improper operating procedures for heavy excavation equipment.

-2.

Other Factors: 1. Operator's contractor human error.

  1. Failure of the gas company to have a full-time inspector at the excavation site.

Probable Cause of Casualties: 1.

Other Casualty Factors: 1.

Recommendations: None

NATIONAL TRANSPONTATION SAFETY BOARD NASHINGTON, D.C. 20594 Drief of Accident

FTW-80-P-PØØ2

Pipoline Accidents:

RY 80., Gtr. 2nd

CompanyType Liquid PipelineCommodityDateLocation
The Texas Pipeline Co.Type Liquid PipelineCrude Oil1/2/80Barwick, Louisiana

Accident: At 9:54 a.m., c.s.t., on January 2, 1980, crude oil leaking from a fracture in a 22-inch Houma-Erath pipeline at a levee crossing at Berwick, LA, flowed under houses along the levee and was ignited by a gas hot water heater. The resulting fire injured two persons, one fatally, destroyed five frame houses and one mobile home. Investigation revealed that the tie-in weld on the levee crossing was reinforced by a full-encirclement fillet-veld aleeve which stiffened the reinforced pipe area and provided stress concentrators at either end of the aleeve where the pipe was weakened by underbead cracking caused by the welding process. An imperfection in the base material, the chemical composition (a high carbon and manganese content), was a factor which increased the hardness of the heat-affected zone and promoted underbead cracking.

LOSSES: Fatalities - 1 - Reportable Injuries - 0 - , Dispeline Damage $110,000 Non-Pipeline Damage $250,000

Probable Causes: 1. Material failure of steel pipe due to use of full-encirclement, fillet-welded sleeve.

Other Factors: 1. Imperfection in base material.

Probable Cause of Casualties: 1. Fatality due to fire as a direct cause of primary loss event.

Other Casualty Factors:

Recommendations:

NATIONAL TRANSPORTATION SAFETY BOARD

NASHINGTON, D.C. 20594 Brief of Accident

DCA-78-FP-1

Pipeline Accident: FY_78, Qtr. 1st

CompanyTypeCommodityDateLocation
People's Gas LightDistributionNatural Gas10/14/774930 W. Cortez Street
and Coke CompanyChicago, Illinois

Accident: Explosion and fire destroyed a two-family house and damaged adjacent buildings. Natural gas had entered the dwelling through a broken service head adapter which was used to connect inserted plastic service lines to the riser and meter set on the inside of the building. The adapter was broken when a contractor, employed by the city, pulled the 1 1/4-inch plastic-encased service line operating at 1/4 psig pressure while removing street curbs. Source of ignition is unknown. The contractor did not notify the utilities of planned excavations as required by the city code.

LOSSES: Fatalities 1, Reportable Injuries 3, Pipeline Damage $700.00 Non-Pipeline Damage $100,000.00

Probable Causes: 1. Damage by human non-pipeline forces due to machine operator error, unaware of pipeline location. 2. Coordination failure, excavator made no effort to determine pipeline existence.

Other Factors: 1.

Probable Cause of Casualties: 1. Fatally burned.

Other Casualty Factors: 1.

Recommendations: P-78-15; P-78-16; P-78-17.

NATIONAL TRANSPORTATION SAFETY BOARD

MASHINGTON, D.C. 20594 Brief of Accident

DCA-80-FP-∞2

Pipeline Accident:

PY 80, Qtr. 1st

CompanyTypeCommodityDateLocation
Central Illinois Light Co.GasDistributionNatural Gas10/13/79Chrisman, Illinois(Edgar County)

Accident: At 1:10 p.m., c.d.t., on October 13, 1979, in Chrisman, Illinois, natural gas at a pressure of 28 peig leaked from the parted seam caused by excavation damage to a 1 1/4-inch scotch-coated steel service line, at its crossing of a water line which had been installed nearly perpendicular to and beneath it some six months previously. The gas migreated beneath and into a one-story, slab-mounted, cement block, newly remodeled commercial building where it was subjected to an unknown source of ignition resulting in an explosion and fire, fatally injuring one person, critically injuring another, and completely destroying the building and contents. Gas servicemen did not respond to a report of gas odors just prior to explosion; and previous odor complaints to owner by tenants were not acted upon.

LOSSES:Fatalities1Reportable Injuries1PipelineNcn-Pipeline
Damage $ 2,000Damage $ 140,000

Probable Causes: 1. Pipeline damaged by backhoe.

  1. Excavator unaware that he had damaged pipeline.
  1. Failure of public to report gas odor.
  1. Human failure to execute emergency procedures properly (respond to leak report).

Other Factors: 1.

Probable Cause of Casualties: 1. Fatality due to smoke inhalation and burns as a result of the primary loss event.

  1. Injury due to burns and collapse of structure as a result of the primary loss event.

Other Casualty Factors: 1.

Recommendations: None

NATIONAL TRANSPORTATION SAFETY BOARD HASHIONGON, D.C. 20594 Brief of Aordant

FTW-78-FP-33-13

Pipeline Accident, FY 78, Ctr. 2nd

CompanyTypeCommodityDateLocation
Hydrocarbon Transportation Inc. (HTI)Pump StationMorpal hurane & ethang-propane mix1/12/78Consey, Kansas

Accident: A liquid pump station was pumping product (normal butane and ethane-propane mix) with its two units when a massive seal leak occurred on one of the pumps. Automatic systems shut down both units in response to leaks, but there was sufficient discharge of product to cause an explosion and fire which in turn damaged closed valves and resulted in further leakage and discharge of product. Both gas-driven turbines, one pump and other pipelines facilities were damaged beyond repair.

LOSES:P�alities 0 , Reportable Injuries 0 , Damage $300,000.00 Damage $--
Probable Causes:1. Material failure of pump shaft seal due to above normal deterioration wear.
2.
3.
Other Factors:1.
2.
Probable Cause of Casualties:1. None
2.
3.
Other Casualty Factors:1. None
2.

NATIONAL TRANSPORATION SAFETY BOARD NASHINGTON, D.C. 20594 Brief of Accident

FT 79-D-P612

Pipeline Accident: FY 79, Qer. 4th

CompanyTypeCorodityDateLocation
Champlin Petroleum CompanyGasNatural Gas8/13/79Knid, Oklahoma

Accident: At 8:15 a.m., c.d.t., on August 13, 1979, a compressor station operator stood partially in front of a scraper trap closure while opening it and the explosive force of rapidly expanding natural gas, which had been confined at an estimated pressure of 100 psig, fatally injured him after tearing the closure off its hinge. He had previously opened the 2-inch blowdown valve 2 or 3 times and had left the valve open, but failed to verify pressure within the 10-inch scraper trap by use of a pressure indicator valve. The 750 psig line pressure, introduced into the trap with an 8-inch polyurethane sphere was not completely relieved because the relatively flexible pig blocked the 2-inch blowdown outlet. The operator was not familiar with the polyurethane pig since this was the first one used in this line. The rigid neoprene pig, normally in use, was effectively prevented from blocking the blowdown outlet by a narrow strip of barstock; the polyurethane pig did block the pressure blowdown opening.

LOSSES: Fatalities 1; Reportable Injuries 0; Damage $1,000 Damage $—

Probable Causes: 1. Failure to properly follow complete procedure ("non use of equipment required by procedures" and unnecessary exposure when opening closure).

Other Factors: 1. "System change made without adequate system test" producing unforeseen consequences.

Probable Cause of Casualties: 1. Fatality due to internal injuries, struck by pipe closure.

a.

a.

Other Casualty Factors: 1.

Recommendations: None

NATIONAL TRANSPORTATION SAFITY BOARD MASHINGTON, D.C. 20594 Brief of Accident

DCA-80-F-P66-6 Company DeKalb-Cherokee Natural

Type Commodity Data Location Gas Distribution Natural Gas 11/17/79 Fort Payne, Dekalb Co., Alabama

Accident: At 1:14 p.m., c.s.t., on November 17, 1979, in Port Payne, Alabama, natural gas leaking from a circumferential fracture in a 4-inch cast iron main operated by DeKalb-Cherokee Natural Gas District at a pressure of 25 pals migrated beneath the foundation of a 4-apartment residential building where it was subjected to an unknown source of ignition. The resulting explosion and fire fatally injured one person, slightly injured three others, destroyed the building, completely destroyed an adjacent building and damaged several others. Metallurgical analysis revealed that graphitization had not weakened the pipe.

LOSSES: Fatalities 1; Reportable Injuries 0; Pipeline 1,000 Damage 120,000

Probable Causes: 1. Material failure of cast iron due to stress induced by frost action and other indeterminate forces.

Other Factors: 1.

Probable Cause of Casualties: 1. Fatality due to fire and asphyxiation as a result of primary loss event.

Other Casualty Factors: 1.

Recomundations: None

NATIONAL TRANSPORTATION SAFETY BOARD

WASHINGTON, D.C. 20594 Brief of Accident

FTW-78-F-P@14

Pipeline Accident: FY 78, Otr. 4th

CompanyTypeCommodityDateLocation
Northwestern Public ServiceDistributionNatural Gas8/28/78Grand Island, Nebraska
Company

Accident: At 10:25 a.m., c.e.t., on August 28, 1978, natural gas which escaped from a 2.7-inch long cir�ferential fracture in a socket heat-fusion coupling on a 2-inch P.E. main operating at a pressure of 40 PSIG, migrated beneath a one-story residence and was subjected to an unknown source of ignition. The resulting explosion and fire injured one person, destroyed the house and damaged three others. Investigation revealed that: (1) the coupling was manufactured with a thermoplastic material which has had a poor service history, (2) the coupling was stressed by subsidence related to aewer construction and a subsequent main extension over the saver 6 years prior to the accident.

LOSSES: Fatalities -0-1 Reportable Injuries -1-1 Pipeline Damage $ 2,000.00 Non-Pipeline Damage $ 189,000.00

Probable Causes: 1. Failure to execute installation procedures properly

Other Factors: 1. Imperfection in base material of plastic fitting (polyethylene coupling).

Probable Cause of Casualties: 1. Injury due to fire as a result of primary loss event.

  1. Injury due to collapse of structure as a result of primary loss event.

Other Casualty Pactors:

Recommendations: P-79-12, P-79-13, P-79-14

MATICIAL TRANSPORTATION SAFITY BOARD

NASHINGTON, D.C. 20594 Brief of Accident

DCA-77-FP-025

Pipeline Accident: FY_77, Qtr. 3rd

CompanyTypeCommodityDateLocation
Carson Gas CompanyDistributionVaporized06/28/77Greenville, North Carolina
Propene Gas

Accident: Explosion and fire destroyed a single family house. A contractor, repairing a septic system, pulled a 3/4-inch propane gas service line operating at 10-15 pals and broke the pipe at a threaded connection. The gas entered the house under the slab foundation and through an opening where the service line riser went through the slab flooring. A flash of fire was seen at the base of the hot water heater seconds before the explosion. The gas was supplied from a 1,000 gallon propane storage tank. The contractor, not knowing the kind of line he had pulled, ignored what possible damage had been done and pushed the pipe back in the ditch without checking for hazards.

LOSSES: Fatalities 2; Reportable Injuries 2; Damage $150.00 Damage $25.000.00

Probable Causes: 1. Damage by human non-pipeline forces due to machine operator error, unaware of pipeline location.

  1. Excavator concealed damage to pipeline.
  1. Human failure : failure to detect escape of gas.

Other Factors: 1.

Probable Cause of Casualties: 1. Fatalities from collapse of structure.

  1. Critically burned.

Other Casualty Factors: 1.

Recommendations: None

NATIONAL TRANSPORTATION SAFETY BOARD

WASHINGTON, D.C. 20594 Brief of Accident

DCA-78-F-P@2

Pipeline Accident: FY_78, Qtr. 1st

Company

Type Commodity Date Location

Southern Connecticut GasDistrubutionNatural Gas10-18-77118i Whitney Avenue
CompanyHamden, Connecticut

Accident: Natural gas leaked from a circumferential break in a 4-inch cast-iron pipe located 2 feet from a 8-unit apartment complex. The gas migrated into the corner apartment and was ignited by some unknown source. Heavy rains and a broken drain line contributed to the erosion of support from beneath the pipe and to the heaving and swelling of the soil around and above the pipe. Graphitization of the pipe wall had weakened it at the point of failure.

LOSSES: Fatalities 2 - ; Reportable Injuries 3 - ; Pipeline Damage $ 3,000 Non-Pipeline Damage $ 80,000

Probable Cases: 1. Graphitization of cast-iron main.

  1. Damage by natural forces: a.) Washout from rain and/or erosion

b.) Earth slide/movement, moisture related.

Other Factors: 1.

Probable Cause of Casualties: 1. Fatally burned.

Other Casualty Factors: 1.

Recommendations: None

NATIONAL TRANSPORTATION SAFETY BOARD

WASHINGTON, D.C. 20594 Brief of Accident

FTW-79-F-P-005

Pipeline Accident: FY 79, Qtr. 2nd

Company
Hastings Utilities
CommodityDateLocation
Natural Gas2-10-79Hastings, Adams Co.,
Nebraska

Accident: At 2:10 a.m., c.s.t., on February 10, 1979, natural gas escaping from a circumferential fracture in an 8-inch cast iron main operating at a pressure of 32 psig migrated into a commercial building where it was subjected to an unknown source of ignition. The resulting explosion and fire destroyed three commercial buildings and damaged many others. There were no casualties. Metallurgical examination revealed that graphitization nearly pernetrated the pipe wall in the area of the fracture. And the pipe had been subjected to frost action during its 50-year service life with the frost line being lower than its 36-inch depth at the time of the accident.

LOSSES: Fatalities - 0 -; Reportable Injuries - 0 -;Pipeline Damage $ 29,000 Damage $4,000,000
Probable Causes: 1. Material failure of cast-iron pipe due to graphitization which weakened material. 2. Damage by frost action.
Other Factors: 1. None
Probable Cause of Casualties: 1. None
Other Casualty Factors: 1. None
Recommendations: None

NATIONAL TRANSPORTATION SAFETY BARD WASHINGTON, D.C. 20594 Brief of Accident

DCA-77-F-P023

Pipeline Accident: FY 77, Qtr. 3rd

CompanyTypeCommodityDateLocation
Citizens Gas and Coke UtilityGas DistributionNatural Gas5/5/77Indianapolis, Ind.

Accident: At 6:00 a.m., c.d.t., on May 5, 1977, natural gas escaping from a 1/4" x 1/2" hole in a 1 1/4-inch steel service riser operating at a pressure of 15 psig was subjected to an unknown source of ignition, exploded and burned, destroying three commercial buildings and damaging three others. The 1 1/4-inch service had been installed in 1956 prior to the requirements for electrical isolation, to serve an inside meter. The hole was partially enclosed in the bottom of an 8-inch concrete slab where the riser from the below-grade service entered the building and ascended to a regulator and meter which were vented to the outside. New, uncorroded metal spatter, on the exterior of the pipe only, covered rust and earth adjacent to the half-moon shaped hole.

LOSSES: Fatalities - 0 - ; Reportable Injuries - 0 - ;Ripeline Damage $ 3,000Non-Pipeline Damage $ 200,000
Probable Causes: 1. Damage by lighting.
2.
3.
Other Factors: 1.
2.
Probable Cause of Casualties: 1. None
2.
3.
Other Casualty Factors: 1.
2.
Recommendations: None

NATIONAL TRANSPORTATION SAFETY BOARD

WASHINGTON, D.C. 20594 Brief of Accident

$$ \text{FTW-79-F-P}\emptyset\emptyset\text{3} $$

Pipeline Accident: FY 79, Qtr. 2nd

CompanyTypeCommodityDateLocation
Lone Star Gas Co.DistributionNatural Gas1/11/79Irving, Texas

Accident: At 2:40 p.m., c.s.t., on January 11, 1979, natural gas leaking from a circumferential opening in a 1-inch steel service line, operating at a pressure of 28 psig, migrated laterally beneath and into a house where it was subjected to an unknown source of ignition. The resulting explosion and fire fatally injured one occupant, critically injured the other, who died 10 days later, and badly damaged the house. Leakage occurred at the readily corroded end of a bare steel nipple where it screwed into an elbow above the service tee. The bare service line was insulated at the meter but not at the mill-wrapped, anode-protected main, resulting in insufficient cathodic protection.

LOSSES: Fatalities 2; Reportable Injuries 0; Pipeline Damage $ 1,000 Non-Pipeline Damage $ 3',000

l. External corrosion due to the lack of cathodic protection.

Other Factors: 1. Earth movement, moisture related, causing direct damage to pipeline.

Probable Cause of Casualties: 1. Fatalities due to fire as a result of primary loss event.

Other Casualty Factors:

Recommendations: None

NATIONAL TRANSPORTATION SAFETY BOARD WASHINGTON, D.C. 20594 Brief of Accident

FTW-78-I-P012Pipeline Accident:Pipeline Accident:PY 78, Qtr. 4thPY 78, Qtr. 4th
FTW-78-I-P012CompanyTypeCommodityDateLocation
Central LouisianaDistributionNatural Gas8-7-78Lafayette, Louisiana
Accident:Natural gas leaking from a corrosion hole in an inactive 1-inch service line "operating" at a pressure of 15 psig, migrated laterally beneath a concrete slab into a building where it was subjected to an unknown source of ignition. The resulting explosion and fire injured 6 persons and destroyed the building and contents. The corrosion hole developed in the steel service at its point of contact with a 4-inch cast-iron sewer line where the coating had been damaged and a bare spot developed. The process of corrosion probably began prior to the installation of anodes, with the steel service being anodic to the cast-iron sewer, according to consultants hired by the operator. The sewer also shielded the service from cathodic protection current.

LOSSES: Fatalities 0; Reportable Injuries 6; Pipeline Damage $ — Non-Pipeline Damage $ —

Probable Causes: 1. External corrosion due to failure of pipe coating because of physical damage; condition not detected.

  1. Inadequate leakage survey procedures for maintenance of gas service line.

"3.

Other Factors: 1.

Probable Cause of Casualties:

  1. Injuries were due to explosion and fire as a direct result of the primary loss event.

Other Casualty Factors:

Recommendations: Pending

NATIONAL TRANSPORTATION SAFETY BOARD

WASHINGTON, D.C. 20594 Brief of Accident

DCA-76-FP-021

Pipeline Accident: FY 79, Otr. 4th

Company Type Commodity Date Locatior

Lewisburg Gas Department Distribution Natural Gas 10/31/76 720 Crestland Drive.

(Municipal)

Accident: At 6:30 c.s.t., October 31, 1976, natural gas which had escaped from a circumferential break in a 2 1/2-inch cast-iron main owned by the Lewisburg Gas Department, operating at a pressure of 15 psig, migrated beneath a one-story house at 720 Crestland Drive, in Lewisburg, Tennessee, exploded and then burned. The gas was ignited by an unknown source. Two people were injured and the house was destroyed. When the gas main break was exposed, it was revealed that the cast-iron main was lying directly on a rock in the bottom of the trench. A large truck hauling creek gravel had been crossing over the pipe, creating a downward force which broke the cast-iron main. Ten days after the accident one of the injured person died.

LOSSES: Fatalities 1; Reportable Injuries 1; Pipeline Damage $250.00_ Non-Pipeline Damage $25,000.00

Probable Causes: 1. Inadequate ditch inspection during construction (no padding under main.)

  1. Overstrasing of pipeline through heavy equipment above pipeline.

Other Factors: 1.

Probable Cause of Casualties: 1. Fire, explosion and injuries from collapse of structure.

Other Casualty Factors: 1.

Recommendations: None

NATIONAL TRANSPORTATION SAFETY BOARD WASHINGTON, D.C. 20594 Brief of Accident

PTA-28-D-P111

Pipeline Accident: PY 78, Qtr.1st

CompanyTypeCommodityDateLocation
CEFIGAS Division ofDistributionNatural Gas11/9/77Lincoln, Nebraska
Minnesota Gas Co.___(Lancaster County)

Accident: The accident was the result of natural gas leakage from a one-inch mill wrapped steel service line which had broken at threads entering a ninety (90) degree elbow because of stress created by installation misalignment. The gas migrated from the thread break, located 14 inches from the block foundation, then through the foundation into the basement where it exploded and burned when ignited by an unknown source. One person was critically injured and later died. The house suffered some structural and fire damage.

LOSSES: Fatalities - 1 - Reportable Injuries - 0 - , Dispiling Damage $ Unknown Non-Pipeline Damage $ Unknown

Probable Causes: 1. Failure to execute installation procedures properly.

Other Factors: 1.

Probable Cause of Casualties: 1. Due to fire as a result of primary loss event.

Other Casuality Factors:

Recommendations: None

NATIONAL TRAMPORTZION SAFETY BOARD HASHINGTON, D.C. 20594 Brief of Accident

FTW-79-F-P@8

Company

Pipeline Accident:

PY 79, Qtr. 3rd

TypeCommodityDateLocation
Natural Gas DistributionNatural Gas4/19/79Mountain View, Santa
Clara Co., California

Accident: On April 19, 1979, a 12-inch steel gas distribution main with a Maximum Allowable Operating Pressure of 153 pasig was struck and ruptured by a bulldozer adjacent to a pipeline marker while it was clearing and grading a fire-break and access road in a rock quarry near Mountain View, California. The escaping gas was ignited by the bulldozer and the resulting fire destroyed the bulldozer and critically injured the operator who died 19 days later.

LOSSES: Fatalities 1; Reportable Injuries 0; Pipeline Damage $10,000 Non-Pipeline Damage $10,000

Probable Causes: 1. Damage by outside party excavator due to machine operator's error in judgement. 2.

Other Factors: 1.

Probable Cause of Casualties: 1. Fatally burned.

Other Casualty Factors:

Recommendations: None

を

NATIONAL TRANSPORTATION SAFETY BOARD MASHINGTON, D.C. 20594 Brief of Accident

PTW-78-D-P15

Company
Nebraska City Utilities

Pipeline Accident:

TypeCommodityDateLocation
Gas DistributionNatural Gas9-1-78Nebraska City, Nebraska

Accident: A pickup truck, driven by a 77-year-old man, departed from the highway and travels over 300 feet to a location 35 feet south of the shoulder of the road where it struck a 4-inch gas transmission line which was operating at a pressure of 600 pig and rose above the ground to a gate valve and regulator installation. The collision, resulting explosion and fire fatally injured the driver, destroyed the pickup, broke the pipeline completely in two, damaged the remainder of the installation, broke an electric pole and 2 guy wires, and interrupted the gas service of 55 customers.

LOSSES: Fatalities - 1 - 1 , Portable Injuries - 0 - 1 , Pipeline Damage $ ? 1 , *Non-Pipeline Damage $ 2,000

Probable Causes: 1. Accidental damage - facility struck by vehicle.

Other Factors: 1.

Probable Cause of Casualties: 1. Fatality due to injuries sustained in motor vehicle accident with fire.

Other Casuality Factors:

Recommendations: None

NATIONAL TRANSPORTATION SAFETY BOARK MASHINGTON, D.C. 20594 Brief of Accident

FTW-78-P-P005

Pipeline Accident: FY_78, Qtr.2nd

Company

Type

Commodity

Date

Location

New Orleans Public Service

Distribution

Natural Gas

2/7/78

New Orleans, Louisiana

Accident: Natural gas escaping from a circumferential fracture in a 16-inch cast-iron main, operating at a pressure of 14 palsig and located beneath a street at a depth of 31 inches, passed through a void beneath the pavement toward the curb and over a storm drain into two raised duplex "garden homes" which were completely destroyed when ignition by an unknown source caused an explosion and fire. Lateral migration of gas through the sever system quickly involved two other buildings - commercial - and residential at either corner and severely damaged them. Occupants of the buildings escaped without injury. The 6-inch cast-iron main was installed in 1927; its 12-foot joints were clamped and concrete was poured over each during the period 1930 - 37. Failures on the 137,890 feet of 16-inch cast-iron, currently in service, total nine. Metallurgical examination revealed that graphitization had partially penetrated the pipe wall.

LOSSES: Fatalities 0 Reportable Injuries 0 Damage 5,709 Damage 150,000

Probable Causes: 1. Material failure of cast-iron pipe due to graphification weakened the material.

Other Factors: 1.

Probable Cause of Casualties: 1.

Other Casualty Factors:

Recommendations: None

NATIONAL TRANSPORTATION SAFETY BOARD MASHINGTON, D.C. 20594 Brief of Accident

PTW-79-F-PØØ4

Pipeline Accident: FY $\_$ 79, Qtr. $\_$ 2nd

CompanyTypeCommodityDateLocation
Lone Star Gas Co.Gas DistributionNatural Gas1/19/79North Richland Hills, Texas

Accident: At 1:10 a.m., c.s.t., on January 19, 1979, natural gas which had escaped from a circumferential fracture at the threads of a 1-inch nipple above the service tap on a 6-inch main, operating at a pressure of 28 psig, migrated laterally beneath and into a house where it was subjected to ignition by a gas-fired furnace or water heater. The resulting explosion and fire killed, one resident, critically injured the other and completely destroyed the house. Gas odors had been detected by the residents but not reported to the gas company. The operator's "swing connection", which is no longer used, was designed to withstand the damaging effect of stress caused by the expansion and contraction of the clay soil as it became vet and then dried. However, the threaded fitting, used contrary to industry standards, was unable to withstand the soil movement. It fractured in the thread which acted as a stress concentrator.

LOSSES: Fatalities 1 , Reportable Injuries 1 , Damage $ 1,000 Mon-Pipeline Damage $ 75,000

Probable Causes: 1. Failure to comply with industry standards.

  1. Soil stress, moisture related (expansion and contraction).
  1. Failure of public (casualties) to report gas odor.

Other Factors: 1.

Probable Cause of Casualties: 1. Fatality due to fire as a result of primary loss event.

  1. Injury due to fire as a result of primary loss event.

Other Casualty Factors: 1.

Recomendations: P-79-27, P-79-28

NATIONAL TRANSPORTATION SAFETY BOARD

WASHINGTON, D.C. 20594

Brief of Accident

FTW-79-F-P913

Pipeline Accident: FY 79, Qtr. 4th

Company

type

Comodity

Date

Location

Cities Service Pipeline Co.

Liquid

Propane

Orange, Texas

Petroleum

8/20/79

(Orange County)

Accident: On August 20, 1979, a bulldozer operated by the Orange County Drainage District, Orange, Texas, began to clean a farm drainage ditch with a generally north-south alignment. After making several passes across the ditch, the operator headed the bulldozer south along the length of the ditch. At 2:15 p.m. the corner of the blade cut into a propane line, owned by the Cities Service Pipe Line Company, which crossed beneath the ditch in an east-west direction. Propane at 350 psig escaped and was ignited within seconds. The resulting fire killed one person and injured another, and caused considerable property damage.

LOSSES: Fatalities 1 Reportable Injuries 1 Damage $190,000.00 Non-Pipeline Damage $99,000.00

Probable Causes: 1. Damage by outside party excavator due to machine operator error, unaware of pipeline existence.

Other Factors:

  1. Coordination failure: No one-call notification requirement.
  1. Coordination failure: Pipeline does not appear on excavator's maps.
  1. Coordination failure: Inexperienced operator did not determine pipeline existence.
  1. Inadequate basic system design (regarding depth of burial which was not required at time of initial construction).

Probable Cause of Casualties: 1. Fatality and injury due to fire as a result of primary loss event. 2.

Other Casualty Factors:

Recommendations: P-80-1, P-80-2, P-80-3-4, P-80-5 through 7

NATIONAL TRANSPORTATION SAFETY BOARD MASHINGTON, D.C. 20594 Brief of Accident

PTW-78-P-P@4

Pipeline Accident:FY 78, Qtr. 2nd
CommodityLocation
Natural Gas1/27/78 Padre Island, Texas
CompanyTypeCommodityDateLocation
Florida Cas TransmissionCompressor StationNatural Gas1/27/78Padre Island, Texas
Company

Accident: A transmission company's remote compressor station developed a natural gas leak which was ignited by one of the engines. The engine stopped instantly when its combustion air was snuffected out, but its vital functions (oil pressure, temperature, suction and discharge pressures, etc.) continued momentarily. The radio alarm relay system became inoperative since it was activated by energy from the engine magneto. The fire weakened the 2-inch bypass between headers which was then ruptured by the discharge pressure and a large volume of gas escaped. The gas volume increased as additional leaks developed. Two of the station's three units were destroyed and the third was severely damaged. Total gas loss was estimated to be 3.24 MMscf.

LOSSES: Fatalities 0; Reportable Injuries 0; Pipeline Damage $500,000 Non-Pipeline Damage $0

Probable Causes: 1. Lack of or inadequate automatic shutoff devices.

  1. Lack of or inadequate control devices.

Other Factors: 1. Base material failure of steel length of pipe due to excessive heat.

Probable Cause of Casualties: 1.

Other Casualty Factors: 1.

Recommendations: P-79-1

NATIONAL TRANSPORTATION SAFETY BOARD WASHINGTON, D.C. 20594 Brief of Accident

FTW-79-P-P@96

Pipeline Accident: FY_79, Qtr.list

Company

Type Commodity Date Location

United Texas Transmission TransmissionNatural Gas10/24/78Pearland, Texas

Company

Accident: At 3:00 a.m., c.s.t., on October 24, 1978, natural gas escaping from a ruptured 30-inch pipeline operating at a pressure of 560 pasg was subjected to an unknown source of ignition, exploded and burned. There were 6 fatalities and 47 injuries resulting from the fire. One house, a barn and 7 mobile homes were destroyed and several were damaged. Thirteen vehicles were destroyed and several damaged. The extent of damage may be related to encroachment by the trailers on the pipeline right-of-way with the destroyed house located 40 feet from the point of rupture and the mobile home park located adjacent to the 50-foot pipeline right-of-way. The considerable delay in shutting off the flow of gas was due to the erroneous indication that the parallel 24-inch line had failed but the delay apparently was not a factor which affected the casualties. Metallurgical analysis revealed that the failure was due to hydrogen cracking (or possible stress corrosion cracking).

LOGES: Fatalities 6 Reportable Injuries 47 Disage $ — Damage $ —

Probable Causes: 1. The pipeline failure was due to hydrogen stress cracking.

-3.

Other Factors: 1.

Probable Cause of Casualties: 1. The fatalities and injuries were due to fire as a result of the primary loss event.

Other Casualty Factors: 1.

Recommendations: None

NATIONAL TRANSPORTATION SAFETY BOARD

WASHINGTON, D.C. 20594 Brief of Accident

FTW-78-FP-011

Pipeline Accident: FY 78, Qtr. 3rd

Company

Type Commodity Date Location

Arizona Public Service Co.

Distribution Natural Gas 6/30/78 Phoenix, Arizona (Maricopa County)

Accident: The accident was the result of a natural gas leak from a fracture caused by the improper installation of a 2-inch Acrylonitrile Butadiene Styrene plastic main in a common trench with a telephone cable. Approximately 4 to 5 feet of the cable were overlaid by the plastic pipe. Tamping and settlement of backfill material created ovality in the supported degment of pipe, with stress and time causing the fracture. Natural gas escaping from this fracture in the main, operating at a pressure of 29 psig migrated through highly permeable soil, beneath a slab and upwards into a house where ignition by an unknown source resulted in one fatality, five injuries, one house destroyed, two others extensively damaged and eleven other homes partially damaged.

LOSSES: Fatalities 1; Reportable Injuries 5; Pipeline Damage $ 5,000 Non-Pipeline Damage $ 300,000

Probable Causes: 1. Improper construction.

  1. ……

Other Factors: 1. Inadequate ditch inspection during construction.

  1. Inadequate lower-in inspection during construction.

Probable Cause of Casualties: 1. Fatality due to injuries from collapse of structure due to primary loss event.

  1. Injuries due to fire and collapse of structure due to primary loss event.

Other Casualty Factors:

Recommendations: None

NATIONAL TRANSPORTATION SAFETY BOARD

WASHINGTON, D.C. 20594

Brief of Accident

FTW-79-F-PØ14

Pipeline Accident:

FY 79, Qtr. 4th

CompanyTypeCommodityDateLocation
Dow Chemical USALiquidNatural Gas9-4-79Pierre Part, Assumption
GatheringLiquids
Parish, Louisiana

Accident: At 12:15 p.m., c.d.t., on September 4, 1979, the tugboat "White Face," towing the barge "Intercoastal 103" in Lake Verret below Pierre Part, LA, backed into and ruptured a 10-inch Dow Chemical, U.S.A.�. pipeline containing natural gas liquids under a pressure of 640 psig. The resulting explosion and fire were responsible for two fatalities, one injury, destruction of the tugboat, barge, and severe damage to the swamp-buggy backhoe on the barge. The pipeline had only 2 feet of cover and was within 5 feet of the water surface of the point of rupture, as indicated by a postaccident survey.

LOSSES:Fatalities - 2 - ;Reportable Injuries - 1 - ;Pipeline Damage $ 240,000Non-Pipeline Damage $ 245,000

Probable Causes: 1. Pipeline damaged by tugboat (operator error - failed to follow instructions).

  1. Failure to comply with Federal regulation (inadequate depth of burial as required by Corps of Engineers Section 10 Permit)
  1. Improper/inadequate pipeline construction/inspection.

Other Factors: 1.

Probable Cause of Casualties: 1. Fatalities and injury due to fire/asphyxiation as a result of primary loss event.

Other Casualty Factors: 1.

Recommendations: None

124 NATIONAL TRANSPORTATION SAPETY BOARD

WASHINGTON, D.C. 20594

Brief of Accident

DCA-79-F-P-021

Pipeline Accident: FY 79, Qtr. 4th

CompanyTypeCommodityDateLocation
The Peoples Natural Gas Co.DistributionNatural Gas7/31/79Pittsburgh, Pennsylvania
Allegheny County

Accident: A man entering a small cellar beneath the office of a commercial greenhouse, struck a match to light his cigarette, a flash fire resulted, burning him critically and resulting in minor damage to the cellar. The man died later that night. A 12-inch, bare-steel, 80-psig pressure main running from south to north, and west of the west building line was excavated 16 feet south of the south building line and 5 feet west of the west building line where two (2) corrosion-caused leaks were found and repaired the same evening. Four additional corrosion leaks and one leaking clamp were repaired later. A 4-inch hole in the greenhouse was located approximately 18 feet from the gas main. The leaking gas could have entered the greenhouse cellar through this drain hole.

LOSSES: Fatalities 1 Reportable Injuries - 0 - ; Pipeline Damage $ - Non-Pipeline Damage $ 500

Probable Causes: 1. Material failure due to corrosion.

  1. Corrosion survey of this bare steel main had not been made to determine if active corrosion existed.

-3.

Other Factors: 1.

Probable Cause of Casualties: 1. Fatality due to fire.

Other Casualty Factors: 1.

Recommendations: P-79-34, P-79-35 through 37

NATIONAL TRANSPORTATION SAFETY BOARD WASHINGTON, D.C. 20594 Brief of Accident

JCA-79-FP-020Pipeline Accident:P.X 79, Qtr. 4thP.X 79, Qtr. 4th
CompanyTypeCommodityDateLocation
Atlanta Gas Light CompanyDistributionNatural Gas07/25/79Roswell, Georgia

Accident: At approximately 8:10 a.m., e.d.t., July 25, 1979, near Roswell, Georgia, a contractor was boring a 20-inch hole under a county road when the cutting head on the auger penetrated a 4-inch plastic main. Natural gas at 54 psig pressure migrated through the bore hole into the bore pit where it ignited. Ignition was from the diesel engine used to power the auger. A workman in the pit received fatal burns; the fireman received hand and arm burns while rescuing the workman still in the pit. The two way gas flow was stopped in approximately two hours by pinching the plastic main a short distance east of the rupture with a hydraulic vice, and closing a valve at the end of a 6-inch connecting section of steel pipe just west of the rupture. The 4-inch plastic gas main was not marked for this specific project, nor was a request made to the gas company to mark the gas main for this specific project.

LOSSES: Fatalities 1 ; Reportable Injuries 1 ; Pipeline Damage $600.00 Non-Pipeline Damage $3,500.00

Probable Causes: 1. Damage by outside contractor; non-pipeline damage by failure of the contractor to make the necessary calls for utility locations.

Other Factors: 1. None

Probable Cause of Casualties: 1. Fatal burns.

Other Casualty Factors: 1. None

Recommendations: None

NATIONAL TRANSPORTATION SAFETY BOARD

WASHINGTON, D.C. 20594

376 · Arief of Accident

DCA-79-FP-007

Pipeline Accident: FY 79, Qtr. 4th

Company Type Commodity Date Location

Consumers Power CompanyDistributionNatural Gas01/16/791014 E 6th Street
Royal Oak, Michigan

Accident: At approximately 5:00 a.m., e.d.t., in January 16, 1979, a natural gas explosion and fire destroyed the residence at 1014 East Sixth Street on Royal Oak, Michigan. Natural gas leaking from the broken threads of a 2 3/8 inch steel main screwed into a 2-inch pipe coupling migrated under frost and frozen earth, entered the residence where it was ignited from an unknown source. One person was killed and two were injured; adjacent houses and several vehicles were also damaged. The investigation revealed that the accident could have been caused by improper procedures used to backfill an excavation at a threaded and coupled joint in the gas main. Frost and frozen earth at a depth of approximately 22 inches was a contributing factor in the migration of the gas.

LOGSES: Fatalities 1; Reportable Injuries 2; Pipeline Damage $3,500.00 Non-Pipeline Damage $80,000.00

Probable Causes: 1. Improper backfill over a 2-inch threaded and coupled steel gas main.

  1. Improper support under the coupling and pipe prior to backfill.

Other Factors: 1.

Probable Cause of Casualties: 1. Critically burned.

  1. Injuries from burns and collapse of structure.

Other Casualty Factors: 1.

Recommendations: None

NATIONAL TRANSPORTATION SAFETY BOARD WASHINGTON, D.C. 20594 Brief of Accident

DCA-79-FP-22

Pipeline Accident: FY 79, Qtr. 4th

Company

Type

Commodity

Date

Location

Washington Gas Light Company

Natural Gas

8/15/79

Seat Pleasant, Maryland

Accident: A contractor, while excavating for an addition to the house involved, struck a 3/4-inch steel service line, breaking it between the cut off valve and drip tee inside the house. Gas at 18 Pig pressure was blowing directly into the house for about 10 minutes. The contractor went into the basement of the house to see if he could cut off the flow of gas. At this point ignition occurred from an unknown source. The contractor is seriously burned. The contractor did not use the one-call system in Prince Georges County for location of utilities. The gas company was unaware of construction around the gas service.

LOSSES: Fatalities 0 Reportable Injuries 1 Damage $600.00 Damage $130,000.00

Probable Causes: 1. Damage by Human Error: Non pipeline-damage by failure of contractor to use the Prince George's County one-call system for line location.

Other Factors: 1.

Probable Cause of Casualties: 1. Injury was from explosion and fire

Other Casualty Factors:

  1. None

Recommendations: None

NATIONAL TRANSPORTATION SAFETY BOARD WASHINGTON, D.C. 20594 Brief of Accident

PTW-78-FP-001

Pipeline Accident:

py 78., Qtr. 1st

CompanyTypeCommodityDateLocation
Arkansas Louisiana Gas CompanyTransmissionNatural Gas10/30/77Shreveport, Louisiana

(ARKLA)

Accident: A city bulldozer was assisting the fire department extinguish a smoldering fire at an abandoned city landfill. Its blade struck an 8-inch transmission line carrying natural gas at a pressure of 260 p�. The threaded and coupled pipe pulled apart. The escaping gas ignited, severely burning the bulldozer operator and he died 16 days later. Four others were burned and two required lengthy hospitalization. The bulldozer and lowboy were destroyed. The operator's shutdown interrupted service to 75 customers.

Pipeline Non-Pipeline Damage $12,000.00 Damage $12,000.00

LOSSES: Fatalities 1 , Reportable Injuries 2 , Damage $12,000.00 Damage $12*,000.00 Probable Causes: 1. Damage by outside party excavator due to machine operator error, unaware of pipeline existence.

Other Factors: $\ldots$ 1.

Probable Cause of Casualties: 1. Due to fire as a result of primary loss event.

Other Casualty Factors:

Recommendations: None

NATIONAL TRANSPORTATION SAFETY BOARD

WASHINGTON, D.C. 20594

Brief of Accident

FTW - 79- DP- 009

Pipeline Accident: FY_79, Qtr. 3rd

Company

Type

Comodity

Date

Location

Delhi Gas Pipeline

Gas

Natural

05/25/79 Slapout. Oklahoma

Corporation

Gathering

Gas

Accident: At 7:00 p.m., c.d.t., on May 25, 1979, natural gas under a pressure of approximately 800 pasig blew a unibolt closure and hinged support off of a 10-inch scraper launcher/receiver when a company employee apparently attempted to remedy a seal leak at the coupling by striking it with a 10-pound brrs- sledgehammer without first blowing down the equipment to reduce the pressure. The company employee stood in front of the closure while striking it, and the explosive force of rapidly expanding natural gas at 800-psig pressure hurled him against a launcher/receiver on a 6-inch pipeline located behind him. Injuries received by this man were fatal.

LOSSES: Fatalities 1; reportable injuries 0; Damage $1,000 Non-Pipeline Damage $

Probebie Causes: 1. Improper operating procedures for a scraper trap.

  1. Improper procedures for maintenance of a scraper trap.

Other Factors: 1.

Probable Cause of Casualties: 1. Fatality due to explosive force as a result or primary loss event.

Other Casualty factors:

  1. Inadequate maintenance of scraper trap closure.
  1. Improper leak repair procedure by use of hammer prior to pressure relief.

NATIONAL TRANSPORTATION SAFETY ZOARD MASHINGTON, D.C. 20594 Brief of Accident

FTW-79-D-PØØ7

Pipalina Accident:

py 79 , Qtr.2nd

CompanyTypeCommodityDateLocation
Rocky Mountain NaturalGas DistributionNatural Gas3/30/79Snowmage Village, Almont Co., Colorado

Accident: Natural gas leaked from a fractured 2-inch plug valve on a gas main and migrated into a building where it was ignited by an unknown source, exploded and burned totally destroying the six-unit, three-story condominium. The valve failure was the result of hillside soil movement in reaction to freezing as thawing. The odor was detected on the night before the accident but not reported.

LOSSES: Fatalities 0 Reportable Injuries 2 Dispirelage $ 2,000 Damage $ 800,000

Probable Causes: 1. Natural forces - earth movement, temperature related (freeze-thaw cycle).

Other Factors: 1. Failure of public to report gas odor promptly.

Probable Cause of Casualties: 1. Injuries from fire.

  1. Injuries from collapse of structure.

Other Casualty Factors:

Recommendations: None

NATIONAL TRANSPORTATION SAFETY BOARD WASHINGTON, D.C. 20594 Brief of Accident

FTW-78-FP-FF2

Pipeline Accident: FY 78_ , Qtr. 1st_

CompanyTypeCommodityDateLocation
Mid America Pipeline SystemGatheringPropane11/8/79Sterling City, Texas
Line

Accident: A pipeline contractor's ditching machine ruptured a 4-inch propane gathering line under a static pressure of 500 psig. Three hours after the rupture, the pipeline contractor's superintendent, who had re-entered the area and parked his pickup truck 650 feet from the break, attempted to start his truck. The explosion and fire critically burned the superintendent, who died 40 days later. The ditching machine, truck and several acres of pasture were destroyed, and 1,530 barrels of propane were lost. The pipeline company which engineered the line being ditched by the contractor did not provide maps to indicate the location of the propane line.

LOSSES: Fatalities 1 ; Reportable Injuries ______, Disage $18,360.00

Probable Causes: 1. Damage by outside party excavator due to machine operator error, unaware of pipeline existence.

  1. Failure of personnel to detect hazardous conditions due to error in judgement.
  1. Coordination failure, notification system failed to forward pipeline location to excavator.

Other Factors: 1.

Probable Cause of Casualties: 1. Fatally burned.

Other Casualty Factors:

Recommendations: None

NATIONAL TRANSPORTATION SAFETY BOARD

NASHINGTON, D.C. 20594 Brief of Accident

DCA-78-FP-@9

CompanyTypeCommodityDateLocation
Bay State Gas CompanyDistributionNatural Gas1/25/78458 Canton Street
Stoughton, Massachusetts

Accident: Natural gas at 45 psig leaked from a fractured 6-inch steel main and migrated under a paved street and frczen earth into a residential dwelling. The gas was ignited by some unknown source. The building was destroyed and one person killed. Excavation of the failed pipe showed that the rupture occurred at a relded joint. The pipe was installed in 1948, prior to federal regulations. A fire continued to burn in the lawn and above the fractured main until valves were located and turned off 5 1/2 hours after the explosion. One valve isolating the leak failed to seal and a valve closer to the leak was finally closed and it held. This valve was overlooked during the initial shutdown.

LOSSES: Fatalities 1; Reportable Injuries 2; Pipeline Damage $3,000.00 Non-Pipeline Damage $40,000.00

Probable Causes: 1. Construction defect - failure of substandard weld.

  1. Inadequate welding inspection during construction.

Other Factor: 1.

Probable Cause of Casualties: 1. Fatally burned.

Other Casualty Factors: 1.

Recommendations: None

NATIONAL TRANSPORTATION SAFETY BOARD

MASHINGTON, D.C. 20594 Brief of Accident

DCA-78-P-P@13

Pipeline Accident: FY 78, Qtr.2nd

CompanyTypeCommodityDateLocation
Ohlo Valley Gas Corp.DistributionNatural Gas2/10/79Sullivan, Indiana

Accident: An outside riser and a 1-inch service, entering the rear of a commercial building to serve an inside meter, was accidentally dislodged by a front end loader clearing snow in the alley. This pulled the service from the meter, resulting in the escape of natural gas at a pressure of 6 inches, w.c. The gas ignited by an unknown source, exploded and burned. Four people were killed, including two gas servicemen who had responded promptly to the leak call. The building was destroyed and the adjacent one was damaged.

LOSSES: Fatalities 4; Reportable Injuries 1; Pipeline Damage $ 4 4 4; Mon-Pipeline Damage $ 4 4 4;

Probable Causes: 1. Overstressing of inside service line due to snow and ice removal by front-end loader adjacent to outside service riser.

Other Factors: 1.

Probable Cause of Casualties: 1. Due to fire, aphyxiation and injuries from collapse of structure.

Other Casualty Factors: 1.

Recommendations: None

NATIONAL TRANSPORTATION SAFETY BOARD WASHINGTON, D.C. 20594

Brief of Accident

LAX-78-FP-001

Pipeline Accident: FY 77, Qtr. 1st

CompanyTypeCommodityDateLocation
Arizona Public Service Co.DistributionNatural Gas12/10/77Tempe, Arizona

Accident: Explosion and fire destroyed a four-unit apartment complex. Natural gas at 38 psig leaked from a crack in a 2-inch plastic Acrylonitrile Butadiene Styrene main. The gas migrated through the ground under a paved parking area and into the building 35 feet away. The gas was ignited when an occupant lit a cigarette. The main hed 35 inches of cover and excavation revealed that the 2-inch pipe had been damaged previously and a piece of tape had been applied to the damaged area by non-pipeline personnel. The fire was extinguished in one hour.

LOSSES: Fatalities 2; Reportable Injuries 3; Pipeline Damage $1,000.00 Non-Pipeline Damage $98,000.00

Probable Causes: 1. Overstressing of pipeline through heavy equipment above pipeline.

  1. Specific cause unknown.

Other Factors: 1.

Probable Cause of Casualties: 1. Critically burned

  1. Injuries from coll-pse of structure

Other Casualty Factors:

Recommendations: None

NATIONAL TRANSPORTATION SAFETY BOARD

WASHINGTON, D.C. 20594

Brief of Accident

PTW-78-I-007

Pipeline Accident:

PY 78 , Qtr. 3rd

CompanyTypeCommodityDateLocation
LoVaca Gathering CompanyTransmissionNatural Gas4/7/78Weimar, Texas
(Colorado County)

Accident: Two men were performing routine calibration and maintenance on a gray cast-iron, positive displacement meter at a town border station, while serving the city on bypass, when the meter exploded, injuring both persons and interrupting service to 798 customers. The meter exploded at something less than the full inlet pressure of 165 psig when the downstream prover valve was closed before the meter reached line pressure and pressure on either side of the dishagrags equalized. Metallurgical examination revealed the existence of casting defects which weakened the case. The 49-year-old meter with a working pressure of 250 psig had been tested at least once to twice its working pressure, but had been used in many locations without additional strength tests. The company meter repair shop had no facilities capable of testing meters to more than 100-psig pressure. The bulky 900-lb meter had been bumped and dented in handling and additional stresses had been imposed by the tightening of its screws each time it was reassembled. Pipeline Non-Pipeline

Pileline $7,743$

Probable Causes: 1. Improper procedure for maintenance (strength testing) of iron-case meters.

  1. Manufacturing defects in iron-case meter due to error in manufacturing procedures.
  1. Material failure of iron-case meter due to (possible) previous damage which weakened material.

Other Factors: 1.

Probable Cause of Casualties:

  1. Injury from flying objects (fragments of meter case) due to primary loss event.

Other Casualty Factors:

Recommendations: None

NATIONAL TRANSPORTATION SAFETY BOARD WASHINGTON, D.C. 20594 Brief of Accident

DCA-78-F-P004

Pipeline Accident: FY_78, Qtr. ist

Company

Type Commodity Date Location

Indiana Gas Co., Inc.

Distribution Natural Gas 11/24/77 West Lafayette, Indiana

Accident: Natural gas leaking from a circumferential break in a 6-inch cast iron main (located at a depth of 26 inches) migrated about 5 feet to a perpendicular sanitary sewer, through the backfill in the sewer trench and under a house built upon a concrete slab. Part of the gas entered the house through floor heating conduits and was limited at 2:05 a.m., e.s.t., on November 24, 1977, when an occupant attempted to light a cigarette with a lighter. An explosion and fire resulted. The residence was damaged and both occupants were injured. One died 11 days later as a result of burns. Metallurgical analysis attributed the failure to graphitization and/or material failure. There was no suggestion of stress other than that induced by temperature change.

LOSSES: Fatalities 1; Reportable Injuries 1; Pipeline Damage $ 3,000 Non-Pipeline Damage $ 10,000

Probable Causes: 1. Material failure of cast-iron pipe due to graphitization which weakened material.

Other Factor: 1.

Probable Cause of Casualties: 1. Due to fire as result of primary loss event.

Other Casualty Factors:

Recommendations: None